8.2.FUN2, FUN4 - UNIVERSAL HARDWARE INPUT
CONFIGURATIONS WITH FLOWMETER MODE
) and
7.8.6. Logical Channels - Math
Task:
The task is to measure four temperatures in the production hall by using a K-type
thermocouple. If all temperatures are greater than the preset value of
140 ° C
, in a separate
channel (alarm condition) the inscription
-HI-
is to be displayed, in other cases
-LO-
is
displayed. All the logical channels and the channel with the temperature alarm condition will
be displayed in one window in the values mode.
Solution:
Before measuring temperature the thermocouple sensors should be connected to the
device. An example of the connection is shown in
Fig. 7.68. Schematic diagram for the
FUN4
hardware configuration
In the first step you need to define five logical channels respectively for four