– Fit the two red ‘O’ rings into the grooves in each end of the
flue turret.
– Engage the flue turret into the air duct assemble, ensuring
the ‘O’ ring is correctly located and the air duct meets up
to the external swage on the turret.
– Secure together with the junction collar and clamp provided.
– Remove the five fixing screws securing the sealed cham-
ber front panel then remove the panel.
– Place the gasket under the flange of the elbow and fit the
elbow unto the top of the appliance, taking care to ensure
that the ‘O’ ring seal is correctly located. This must be
checked from inside the sealed chamber.
– Secure the elbow onto the top of the appliance using the
four screws provided.
– Refit the sealed chamber front panel.
3.4.3 Standard flue
– Push the flue duct assembly into the air duct until the
external swaged ring on the flue terminal stops against
the internal swage on the air duct (fig. 11).
– Fit the rubber sealing ring into the swaged groove in the air duct
as shown in fig. 13. Ensure that it is the correct way around.
– From inside or outside the building, slide the duct assem-
bly into the wall until the sealing ring forms a good seal
against the outside wall.
– With reference to fig. 13, slide on the aluminium retention
ring (D), check that the rubber sealing ring (E) is pulled up to
the wall and that the duct assembly is horizontal, then
secure the aluminium retention ring to the air duct using the
two screws (H) provided. Do not overtighten the screws.
– Push the junction collar (B) over the air duct until the air
duct touches the inner part of the collar where the diame-
ter becomes smaller.
– Push the elbow socket into the junction collar and onto the
flue duct.
– Fit the jointing clamp (I) over the junction collar.
9
Fig. 10
Telescopic flue
NOTE: the kit can be extended to a maxi-
mum length of 580 mm horizontal.
Fig. 12
TABLE 7
Horizontal coaxial duct lenght (Z fig. 10-13)
from 380 to 580 mm from 580 to 1500 mm from 1500 to 3000 mm
Standard diaphragm
Optional diaphragm
Diaphragm
Superior 40 Ci
Ø 79
Ø 84 (Code 6028622)
-
Superior 50 Ci
Ø 81
Ø 84 (Code 6028622)
-
Superior 60 Ci
Ø 81
Ø 84 (Code 6028622)
-
Superior 80 Ci
Ø 84
Ø 87,5 (Code 6028624)
-
Vertical coaxial duct lenght
from 1300 to 2500 mm
from 2500 to 4000 mm
Standard diaphragm
Optional diaphragm
Superior 40 Ci
Ø 79
Ø 84 (Code 6028622)
Superior 50 Ci
Ø 81
Ø 84 (Code 6028622)
Superior 60 Ci
Ø 81
Ø 84 (Code 6028622)
Superior 80 Ci
Ø 84
Ø 87,5 (Code 6028624)
KEY
A
Elbow
B
Junction collar
C
Outer duct
D
Inner rubber sealing ring
F
Neoprene gasket
G
Protective metal collar
H
Inner lip seal
Push flue duct and terminal into air duct from this end.
Fig. 11