ction.and.the.display.will.show.the.alarm.
“ALL.05”.
–. FLAME BLOCK ALARM 06 (fig. 24/e)
. If.the.flame.control.has.not.detected.the.
presence.of.the.flame.after.a.complete.
ignition.sequence,.or.for.any.other.rea-
son.the.card.cannot.“see”.the.flame,.the.
boiler.will.stop.and.the.display.will.show.
the.alarm.“ALL.06”..
. Press.the.key.
5
3
1
2
4
.of.the.controls.(2).to.
start.up.the.boiler.again.
–. SAFETY
THERMOSTAT
ANOMALY
ALARM 07 (fig. 24/f)
. If.the.connection.with.the.safety.thermo-
stat. is. interrupted,. the. boiler. will. stop;.
the.flame.control.will.remain.waiting.to.
be.switched.off.for.one.minute,.keeping.
the.system.pump.on.for.that.period..
. If,.the.thermostat.connection.is.restored.
within.the.minute,.the.boiler.will.start.up.
working.normally.again,.otherwise.it.will.
stop.and.the.display.will.show.the.alarm.
“ALL.07”.
. Press.the.key.
5
3
1
2
4
.of.the.controls.(2).to.
start.up.the.boiler.again.
. If.the.alarm.reappears.after.it.was.rele-
ased,.wait.the.thermostat.sensor.to.cool.
and.then.repeat.again.the.release..
–. PARASITE FLAME ANOMALY ALARM 08
(fig. 24/g)
. If. the. flame. control. section. recognises.
the. presence. of. flames. also. in. phases.
when.they.should.not.be.present,.it.me-
ans. there. is. a. breakdown. in. the. flame.
detection.circuit;.the.boiler.will.stop.and.
the.display.will.show.anomaly.“ALL.08”.
–. AUXILIARY SENSOR ANOMALY ALARM
10 (fig. 24/l)
. BOILER. WITH. ACCUMULATION:. ano-
maly.of.the.D.H.W..sensor.(SB)..When.the.
D.H.W..sensor.is.open.or.short.circuited,.
the.display.will.show.anomaly.“ALL.10”..
The.boiler.will.function.but.will.not.mo-
dulate.power.for.the.D.H.W.
BOILER.ONLY.FOR.HEATING:.antifreeze.
sensor. anomaly. for. boilers. which. fore-
see.the.use.of.antifreeze.sensors.
. When.the.sensor.is.open.or.short.circu-
ited,.the.boiler.loses.part.of.its.anti-fre-
eze. functions. and. the. display. will. show.
anomaly.“ALL.10”.
. BOILER. COMBINED. WITH. SUN-PANEL.
SYSTEM:. anomaly. of. the. D.H.W.. input.
sensor..When.the.sensor.is.open.or.short.
circuited,.the.boiler.loses.the.sun-panel.
function.and.the.display.will.show.ano-
maly.“ALL.10”...
–. MODULATOR ANOMALY “ALL 11” (fig.
24/m)
. Anomaly.modulator.disconnected..When.
during. operation. the. boiler. detects. no.
current.to.the.modulator,.the.display.will.
show.anomaly.ALL.11.
. The boiler operates at minimum power
and the anomaly is deactivated when
the modulator is reconnected or when
the burner stops working.
–. CONFIGURATION ANOMALY “ALL 12”
(fig. 24/n)
. Anomaly.configuration.SEALED./.OPEN..
A.possible.inconsistency.between.the.va-
lue.set.by.the.installer.to.the.PAR.1.and.
the. self-recognition. of. the. card. causes.
the. activation. of. this. anomaly,. the. boi-
ler.stops.working.and.the.display.shows.
anomaly.ALL.12.
. Reconfigure. the. PAR. 1. to. desable. the.
anomaly.
–. SAFETY THERMOSTAT INTERVENTION
FIRST MIXED ZONE “ALL 20” (fig. 24/p)
. When.it.results.that.the.ZONA.MIX.board.
is.connected.to.the.boiler.the.safety.ther-
mostat. intervention. switches. the. mixed.
zone.plant.pump,.the.mix.zone.valve.clo-
ses.and.on.the.display.the.anomaly.ALL.
20..
. During.this.anomaly.the.boiler.continues.
to.function.normally..
–. DELIVERY PROBE BREAKDOWN ANO-
MALY FIRST MIXED ZONE “ALL 21” (fig.
24/q)
. When.it.results.that.the.ZONA.MIX.board.
Fig..24/l
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Fig..24/m
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Fig..24/g
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Fig..24/f
Fig..24/d
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Fig..24/e
Fig..24/n
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Fig..24/p
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Summary of Contents for RX 19 E
Page 2: ......
Page 32: ...32 NOTES...
Page 62: ...62 NOTES...
Page 63: ...1 64 2 68 3 77 4 84 RX E Fonderie Sime S p A RX E 92 42 CEE 2009 142 CE 2014 30 UE 2014 35 UE...
Page 83: ...3 8 P 17 5 RX 37 48 55 E 12 5 12 83 IT ENG RUS 5 1 2 3 4 17 16 1 2 3 1 2 12 3 4 12 5...
Page 92: ...92 NOTES...
Page 93: ...93 IT ENG RUS NOTES...
Page 94: ...94 NOTES...
Page 95: ......