105
ES
PT
ENG
3.3
ACCESS TO
INSTALLER’S
PARAMETERS
For access to the installer’s parameters,
press simultaneously the keys
and
or 2 seconds (3 fig. 12).
For example, the parameter PAR 23 is
visualised on the display of the control
panel in the following way:
The parameters scroll forwards and
backwards with the key
and
and
the default parameters can be changed
with the keys
and
.
The standard visualisation returns auto-
matically after 60 seconds, or by pres-
sing one of the control keys (2 fig. 12)
excluded the key RESET.
3.3.1
Replacing the board or
RESETTING parameters
If the electronic board is replaced or
reset, it is necessary to configure PAR 1
and PAR 2 by associating the following
values to each type of boiler to be able to
restart the boiler:
GAS
MODELS
PAR 1
25 - 25 T ErP
1
METHANE
30 ErP
2
(G 20)
35 - 35 T ErP
3
25 - 25 T ErP
9
PROPANE
30 ErP
10
(G 31)
35 - 35 T ErP
11
PARAMETERS INSTALLER
FAST CONFIGURATION
PAR DESCRIPTION
RANGE
UNIT OF
INC/DEC
DEFAULT
MEASUREMENT UNIT
SETTING
1
Combustion configuration
-- = ND
=
=
“- -”
1 ... 63
2
Hydraulic configuration
-- = ND
=
=
“- -”
1 ... 14
3
Timetable 2 programmer
1 = DHW + Recirc. pump
=
=
1
2 = DHW
3 = Recirculation pump
4
Pressure transducer disabler
0 = Disabled
=
=
1
1 = Enabled 0-4 BAR
2 = Enabled 0-6 BAR
3 = Enabled 0-4 BAR (NO ALL 09)
4 = Enabled 0-6 BAR (NO ALL 09)
5
Assignment of auxiliary relay AUX 1 = Remote supply
=
=
1
2 = Recirculation pump
3 = Automatic load.
4 = Remote alarm NC
5 = Heat pump
6 = Zone 2 valve
6
Luminous bar indicating presence
0 = Disabled
=
=
1
of voltage
1 = Enabled
7
Allocation of SIME HOME channels
0 = Not assigned
=
=
1
1 = Circuit 1
2 = Three-zone circuit
8
Fan rpm Step ignition
0,0 ... 81
rpmx100
0,1
from 0,1 to 19,9
0,0
1
from 20 to 81
9
Long chimneys
0 ... 20
%
1
0
10 Remote control option setting
1 = SIME HOME
=
=
1
2 = CR 53
3 = RVS 43.143
4 = RVS 46.530
5 = RVS 61.843
11 Correction values external sensor
-5 ... +5
°C
1
0
12 Backlighting duration
-- = Always
sec. x 10
1
3
0 = Never
1 ... 199
13 Modulating pump speed
-- = None
%
10
Au
AU = Automatic mod.
30...100 = % Settable
modulation
14 Setting second input TA
-- = Contact TA
--
--
--
5...160 = Input 0...10VDC
15 Cascade address
-- = Not enabled
--
1
--
0 = Master
1...7 = Slaves
16 ModBus address
-- = Not enabled
--
1
--
1...31 = Slaves
17 ModBus communication configuration 1 ... 30
--
1
25
19 Type circuit
0 = Two zones
--
--
0
1 = Three zones
D.H.W. - HEATING
PAR DESCRIPTION
RANGE
UNIT OF
INC/DEC
DEFAULT
MEASUREMENT UNIT
SETTING
20
Minimum heating temperature Zone 1 PAR 64 OEM ... PAR 21
°C
1
20
21
Maximum heating temperature Zone 1 PAR 20 ... PAR 65 OEM
°C
1
80
22
Heating curve slope Zone 1
3 ... 40
--
1
20
23
Minimum heating temperature Zone 2 PAR 64 OEM ... PAR 24
°C
1
20
24
Maximum heating temperature Zone 2 PAR 23 ... PAR 65 OEM
°C
1
80
25
Heating curve slope Zone 2
3 ... 40
--
1
20
26
Minimum heating temperature Zone 3 PAR 64 OEM ... PAR 27
°C
1
20
27
Maximum heating temperature Zone 3 PAR 26 ... PAR 65 OEM
°C
1
80
28
Heating curve slope Zone 3
3 ... 40
--
1
20
29
∆
t heating circuit
10 ... 40
°C
1
20
30
Post-circulation heating time
0 ... 199
Sec.
10
30
31
Maximum heating capacity
30 ... 100
%
1
100
32
Zone 1 pump activation delay
0 ... 199
10 sec.
1
1
33
Start-up delay
0 ... 10
Min.
1
3
34
Additional source activation threshold -- , -10 ... 40
°C
1
“- -”
35
Boiler antifreeze
0 ... +20
°C
1
3
36
External sensor antifreeze
-5 ... +5
°C
1
-2
37
Band saturation
-- =
Disabled
%
1
100
flowmeter modulation
0 ... 100
38
D.H.W. post-circulation time
0 ... 199
Sec.
1
0
39
Anti-legionella
0 =
Disabled
--
--
0
(only D.H.W tank))
1 =
Enabled