background image

105

ES

PT

ENG

3.4

EXTERNAL SENSOR
(fig. 15)

If there is an external sensor, the heating
settings SET can be taken from the climatic
curves according to the external tempera-
ture and, in any case, limited to with the
range values described in point 3.3 (para-
meters PAR 25 for zone 1 and PAR 26 for
zone 2).
The climatic curve to be set can be selected
from a value of 3 and 40 (at step 1).
Increasing the steepness of the curves of
fig. 15 will increase the output temperature
as the external temperature decreases.

3.5

CARD FUNCTIONING

The electronic card has the following func-
tions:
– Antifreeze protection of the heating and

sanitary water circuits (ICE).

– Ignition and flame detection system.
– Control panel setting for the power and

the gas for boiler functioning.

– Anti-block for the pump which is fed for

a few seconds after 24 hours of inacti-
vity.

– Antifreeze protection for boilers with an

accumulation boiling unit.

– Chimney sweep function which can be

activated from the control panel.

– Temperature which can be shifted with

the external sensor connected. 
It can be set from the control panel and
is active on the heating systems of both
circuit 1 and circuit 2.

– Management of two independent hea-

ting circuit systems.

– Automatic regulation of the ignition

power and maximum heating.
Adjustments are managed automati-
cally by the electronic card to guaran-
tee maximum flexibility in use of the
system.

– Interface with the following electronic

systems: climatic regulator CR 53,
remote control CR 73, thermal regula-
tor RVS, connected to a management
card of a mixed zone ZONA MIX code
8092234 and card solar INSOL code
8092235. 

NOTE: If using CR 53 or RVS set para-
meter 10 to 2 (PAR 10=2). 

– Function anticondensig, preheat the body

("+" sign in front of the main digits) and
anti inertia.

3.6

TEMPERATURE 
DETECTION SENSOR

Table 3

gives the values of the electrical

element (

) obtained on the heating and

sanitary water sensors according to the
variations in temperature. 

When the heating sensor (SM) is inter-
rupted, the boiler will not function for
both services. 

With the D.H.W. sensor (SS) interrupted,
the boiler functions but will not made the
power modulations for the D.H.W.

3.7

ELECTRONIC IGNITION

Ignition and flame detection is controlled by
a single electrode on the burner which gua-
rantees reaction in the case of accidental
extinction or lack of gas within one second.

3.7.1

Functioning cycle

Burner ignition occurs within max. 10
seconds after the opening of the gas valve.
Ignition failure with consequent activation of
block can be due to:

Lack of gas

The ignition electrode persists in dischar-
ging for max. 10 seconds. If the burner
does not ignite, the anomaly is signalled.
This can happen the first time the boiler
is switched on after a long period of inac-
tivity due to the presence of air in the gas
pipes.
It can be caused by a closed gas tap or by

a broken valve coil (the interruption does
not allow for opening). 

The electrode does not discharge.

In the boiler, only the opening of the gas
to the burner can be detected. After 10
seconds the anomaly is signalled.
It can be caused by an interruption in the
electrode wire or if it is incorrectly ancho-
red to the connection points. 
Or the electrode may be earthed or
strongly worn: it must be replaced. 
Or the electronic card may be defective.

In the case of a sudden lack of voltage, the
burner will immediately switch off. When
voltage returns, the boiler will automatically
start up again.

3.8

FUMES THERMOSTAT 
vers. OF

This is a safety measure against the return
of the fumes into the environment due to
an inefficient or partially blocked chimney
(6 fig. 3). 
It reacts by blocking the functioning of the
gas valve when the fumes are continually
forced back into the environment, in a
quantity that can be dangerous. If the boiler
repeatedly stops, it will be necessary to
carefully check the chimney, and to carry
out all modifications and take all measures
necessary to restore it to an ef ficient
working state. After every intervention car-
ried outon the device, check correct func-
tioning. In the case of replacement, use only
original spare parts.

TABLE 3

Temperature (°C)

Resistance (

)

20

12.090

30

8.313

40

5.828

50

4.161

60

3.021

70

2.229

80

1.669

Fig. 15

ATTENTION: curves are calculated at an ambient tempe-
rature of 20°C. The user can act on the boiler controls to
change the environment set  for which the bend has been
calculated by ±5°C. 

Summary of Contents for MURELLE EV 20 BFT

Page 1: ...MURELLE EV Fonderie SIME S p A Cod 6322729 01 2014 ES PT ENG...

Page 2: ......

Page 3: ...i n de los productos de la combusti n est libre y o montado correcta mente Controlar que las eventuales v lvulas est n abiertas Asegurarse que la instalaci n est llena de agua y bien purgada Controlar...

Page 4: ...a c mara combu sti n abierta tiro natural MURELLE EV 25 30 35 BF con encendi do y modulaci n electr nica c mara estanca flujo forzado MURELLE EV 20 25 BFT con encendido y modulaci n electr nica c mara...

Page 5: ...a agua sanitaria G 1 2 UNI ISO 228 1 DIMENSIONES 25 30 35 L mm 400 450 450 K mm 180 205 205 ATENCI N La versi n BFT est preparada para la conexi n de un calentador remoto Para utilizarla como caldera...

Page 6: ...1 1 Campo de regulaci n sanitario C 10 65 10 65 10 65 10 65 10 65 Caudal sanitario espec fico EN 625 l min 10 7 12 7 11 1 13 2 15 3 Caudal sanitario continuo t 30 C l min 10 9 12 9 11 3 13 4 15 5 Cau...

Page 7: ...3 BAR 14 Descarga caldera 16 Transductor presi n agua 18 Caudal metro sanitario 19 Filtro agua sanitaria 20 Cargamento 21 Aqua Guard Filter System 22 Placa uniones empalmes opcional 23 Grifo agua san...

Page 8: ...10 Intercambiador primario 11 Electrodo de encendido detecci n 12 V lvula gas 13 Protecci n empalmes Modelo 25 30 35 BF 20 25 BFT 1 5 COMPONENTES PRINCIPALES fig 3 Fig 3 LEYENDA 1 Panel mandos 2 V lvu...

Page 9: ...lar el aparato proceder al lavado de la instalaci n utilizando productos adecuados como por ejemplo el Sentinel X300 nuevos instalaci n X400 y X800 viejo instalaci n Fernox Cleaner F3 Instrucciones co...

Page 10: ...y max 3 0 m per vers 30 35 40 min 1 3 m max 5 m max 5 0 m per vers 20 max 3 5 m per vers 25 max 3 0 m per vers 30 35 40 LEYENDA 1 Kit conducto coaxial L 810 c d 8084811 2 a Alargadera L 1000 c d 80961...

Page 11: ...falsos encendidos del que mado En estos casos es necesario pre veer un sistema de recogida del conden sado en la tuber a C12 C32 C42 2 7 6 4 1 2 min 4 m max 7 m 8 x y x y min 3 5 m max 6 m 25 x y min...

Page 12: ...80 0 15 0 50 P rdida de carga total 2 25 3 40 5 65 mmH2O Con esta p rdida de carga total hay que quitar del diafragma de aspiraci n los sectores del n mero 1 al n mero 7 inclusive 1 2 3 4 6 165 110 1...

Page 13: ...Curva a 90 MF aislada c d 8077408 3 a Prolongaci n L 1000 n 6 c d 8077309 3 b Prolongaci n L 1000 aislada c d 8077306 3 c Prolongaci n L 500 n 6 c d 807308 3d Prolongaci n L 135 con toma c d 8077304...

Page 14: ...as distancias m nimas que deben ser respetadas presentadas en la Tabla 2 representan indicaciones no vinculantes con referencia a un edificio como el de la fig 11 2 11 CONEXION ELECTRICA La caldera se...

Page 15: ...terna que se suministra bajo pedido c d 8094101 para regular aut nomamente el valor de temperatura de impulsi n de la caldera seg n la temperatura externa Para el montaje seguir las instrucciones del...

Page 16: ...NDA EXTERNA C d 8094101 3 INSTALACI N B SICA INSTALACI N DE VARIAS ZONAS CON BOMBAS TERMOSTATOS AMBIENTE Y SONDA EXTERNA C d 8094101 4 INSTALACI N B SICA INSTALACI N DE VARIAS ZONAS CON V LVULAS TERMO...

Page 17: ...OCHE 50 C AJUSTE DE PAR METROS En caso de uso del mando a distancia CR como referencia ambiente para una zona progra mar PAR 7 1 Programar el tiempo de apertu ra de la v lvula de zona VZ PAR 33 TIEMPO...

Page 18: ...la entrada TA1 R M SE TA2 TA1 SE TA1 SI RL2 P2 P1 PB RL1 BOLLITORE PB SB SB R M SE CT2 TA1 SE CT1 SI RL2 P2 P1 TA2 RL1 ZONA GIORNO 70 C ZONA NOTTE 50 C 8 INSTALACI N CON DOBLE TEMPERATURA DE IMPULSI...

Page 19: ...A MEZCLADA 12 INSTALACI N CON V LVULA DE MEZCLA INSTALACI N CON DOS ZONAS DIRECTAS Y DOS ZONAS MEZCLADAS AJUSTE DE PAR METROS Para utilizar el mando a distancia CR como panel remoto de la caldera y no...

Page 20: ...2 R M SE TA1 SE SI P1 TA2 EXP VM EXP IP TA1 TA2 P2 VM IP EXP EXP INSOL Vers BFT T 14 INSTALACI N SOLAR INSTALACI N CON DOS ZONAS MEZCLADAS INDEPENDIENTES DOS KIT ZONA MIX C d 8092234 Y UN KIT INSOL C...

Page 21: ...ato de seguridad TF Term stato de humos VP V lvula desviadora M Modulador SM Sonda calefacci n SS Sonda sanitaria TPA Transductor de presi n FLM Caudal metro sanitario TA1 Termostato ambiente Zona 1 T...

Page 22: ...odulador SM Sonda calefacci n SS Sonda sanitaria TPA Transductor de presi n FLM Caudal metro sanitario TA1 Termostato ambiente Zona 1 TA2 Termostato ambiente Zona 2 ST Sonda temperatura solar CR Contr...

Page 23: ...viadora TPA Transductor de presi n TA1 Termostato ambiente Zona 1 TA2 Termostato ambiente Zona 2 SB Sonda calentador CR Control remoto CR 73 opcional SE Sonda externa opcional OP Reloj programador opc...

Page 24: ...esta tecla aumenta o disminuye el valor programado ICONO FUNCIONAMIENTO QUEMADOR Y BLOQUEO ICONO NECESIDAD DE RESET ICONO FUNCI N LIMPIACHIMENEAS D GITOS SECUNDARIOS La caldera muestra el valor de pr...

Page 25: ...Visualizzazione codice errore ultima anomalia 15 Contatore accessi parametri installatore es 140 accessi 5 Visualizzazione temperatura sonda fumi 8 Visualizzazione corrente di ionizzazione in A 16 Co...

Page 26: ...EXP config ZONA MIX 36 Visualizzazione stato flussostato solare rispettivamente ON e OFF 17 Visualizaci n caudal sanitario caudal metro 18 l min y 0 31 l min o estado medidor de flujo respectivamente...

Page 27: ...ta 1 s lo calentador 2 B Recirculaci n 6 Barra luminosa presencia tensi n 0 Inhabilitado 1 1 Habilitado 0 No asignado 7 Asignaci n canales CR 73 1 Circuito 1 1 2 Circuito 1 y 2 8 9 1 CR 73 10 Configur...

Page 28: ...ficultad para comprender la configuraci n actual o en caso de comportamiento an malo o no comprensible de la caldera se recomienda restablecer los valores iniciales de los par metros configurando el P...

Page 29: ...la detecci n de llama se con trolan por un electrodo puesto en el que mador que garantiza la m xima seguridad con tiempos de intervenci n por apagados accidentales o falta de gas inferiores a un segun...

Page 30: ...n de calefacci n est representada en fun ci n de la capacidad del gr fico de la fig 17 La velocidad de la bomba modulable se ha configurado con un valor predeterminado par metro del instalador PAR 13...

Page 31: ...mpleando agua y jab n o productos ade cuados evitando el uso de llamas libres 4 2 1 Configuraci n del nuevo combustible de alimentaci n Para acceder a los par metros para el instalador pulsar simult n...

Page 32: ...a Tabla 4 S lo luego de haber efectuado la regula ci n de la presi n m xima regular la m nima Pulsar la tecla manteniendo abierto el grifo de agua sanitaria Mantener bloqueada la tuerca 3 y girar el t...

Page 33: ...ciones Montar las partes desmontadas de la caldera respetando la secuencia correc ta Controlar el funcionamiento del quema dor principal Despu s del montaje probar la estan queidad todas las conexione...

Page 34: ...43 0 Funci n desactivada 1 Configuraci n curva A 2 Configuraci n curva B 3 Configuraci n curva A B El set de la zona mezclada sigue la evolu ci n de la curva seleccionada y llega a un m ximo de 55 C C...

Page 35: ...tocircuito la caldera fun ciona pero no efect a la modulaci n de potencia en fase sanitario En el display se visualiza la anomal a ALL 04 ANOMAL A SONDA CALEFACCI N ALL 05 fig 24 d Cuando la sonda cal...

Page 36: ...om tico efectuado por la tarjeta determina la activaci n de la anomal a la caldera no funciona y en el display se visualiza la anomal a ALL 12 Reconfigu rar el PAR 1 para que la anomal a se desactive...

Page 37: ...rrecta PAR 2 en el display aparece la anomal a ALL 27 Durante dicha anomal a la calde ra sigue funcionando normalmente y en la tarjeta solar permanece activa nica mente la funci n antihielo colector s...

Page 38: ...O Y FUNCIONAMIENTO ENCENDIDO CALDERA fig 25 El primer encendido de la caldera debe ser efectuado por personal t cnico autorizado En lo sucesivo para volver a poner la calde ra en servicio seguir deten...

Page 39: ...de temperatura proporcional calcula do El display se presenta como indica la figura 26 a REGULACI N DE LA TEMPERATURA DEL AGUA SANITARIA fig 27 Para programar la temperatura del agua sanitaria desead...

Page 40: ...a Si la anomal a persiste solicitar la intervenci n de personal t cnico auto rizado ALL 07 fig 28 d Pulsar la tecla del panel de man dos 2 para volver a activar la caldera Si la anomal a persiste soli...

Page 41: ...ada cor rectamente Certifique se que as eventuais v lvulas de corte estejam abertas Certifique se que a instala o tenha sido cheia de gua e esteja sem ar nos tubos Verifique que a bomba circuladora n...

Page 42: ...tiragem natu ral MURELLE EV 25 30 35 BF com acendi mento e modula o electr nica c mara de combust o estanque com fluxo for a do MURELLE EV 20 25 BFT s aquecimen to com acendimento e modula o elec tr n...

Page 43: ...2 UNI ISO 228 1 U Sa da gua sanit ria G 1 2 UNI ISO 228 1 DIMENS ES 25 30 35 L mm 400 450 450 K mm 180 205 205 ATEN O A vers o BFT est predisposta para a conex o a um fervidor remoto para utiliz la c...

Page 44: ...la o sanit rio C 10 65 10 65 10 65 10 65 10 65 Caudal sanit rio espec fico EN 625 l min 10 7 12 7 11 1 13 2 15 3 Caudal sanit rio cont nuo t 30 C l min 10 9 12 9 11 3 13 4 15 5 Caudal sanit rio m nimo...

Page 45: ...16 Transdutor press o gua 18 Flux metro sanit rio 19 Filtro gua sanit ria 19 Torneira retorno circuito opcional 20 Abastecimento 21 Aqua Guard Filter System 22 Placa liga es optional 23 Torneira entr...

Page 46: ...ctrodo de acens o releva o 10 Protec o conex es Modelo 25 30 35 BF 20 25 BFT Modelo 25 30 OF LEGENDA 1 Painel de comandos 2 V lvula desviadora 3 C mara de combust o 4 Ventilador 5 Tomadas de an lise d...

Page 47: ...ica contra as corros es incrusta es ou dep sitos de m xima import ncia antes a instala o do aparelho proceder lavagem do mesmo confrome a norma UNI CTI 8065 utilizando produtos apropriados como por ex...

Page 48: ...er vers 25 x y max 3 0 m per vers 30 35 40 min 1 3 m max 5 m max 5 0 m per vers 20 max 3 5 m per vers 25 max 3 0 m per vers 30 35 40 LEGENDA 1 Kit de conduta coaxial L 810 c d 8084811 2 a Extens o L 1...

Page 49: ...talar na tubagem um sistema de recolha da con densa o Em caso de atravessamento de paredes inflam veis isolar o tro o de atravessa mento da conduta de descarga dos fumos com l de vidro de 30 mm de C12...

Page 50: ...2 25 3 40 5 65 mmH2O Com esta perda de carga total necess rio retirar do diafragma de aspira o os sectores do n mero 1 ao n mero 7 inclusive 1 2 3 4 6 165 110 165 K 80 80 100 92 Fig 8 Fig 8 a Fig 7 L...

Page 51: ...408 3a Extens o L 1000 n 6 c d 8077309 3b Extens o L 1000 isolada c d 8077306 3c Extens o L 500 n 6 c d 8077308 3d Extens o L 135 com tomada c d 8077304 4 Terminal de evacua o c d 8089501 5 Kit aros i...

Page 52: ...ultar a Tabela 1 2 10 POSICIONAMENTO TERMINAIS DE DESCARGA fig 11 Os terminais de descarga para aparelhos de tiragem for ada podem ser situados nas paredes externas do edif cio A t tulo indicativo e n...

Page 53: ...isposta para a liga o a um regulador clim tico fornecido por encomenda c d 8092227 para a gest o de um circuito de aquecimento A placa electr nica continuar a gerir a visualiza o das informa es a conf...

Page 54: ...A EXTERIOR C d 8094101 3 INSTALA O BASE INSTALA O MULTIZONA COM BOMBAS TERM STATOS AMBIENTE E SONDA EXTERIOR C d 8094101 4 INSTALA O BASE INSTALA O MULTIZONA COM V LVULAS TERM STATOS AMBIENTE COMANDO...

Page 55: ...xterior aceder confi gura o da zona dia 1 pressionan do a tecla e modificar o valor com as teclas e Entrar na configura o da zona noite 2 pressionando duas vezes a tecla modificar o valor com as tecla...

Page 56: ...r um TA ligado entrada TA1 R M SE TA2 TA1 SE TA1 SI RL2 P2 P1 PB RL1 BOLLITORE PB SB SB R M SE CT2 TA1 SE CT1 SI RL2 P2 P1 TA2 RL1 ZONA GIORNO 70 C ZONA NOTTE 50 C 8 INSTALA O COM TEMPERATURA DUPLA DE...

Page 57: ...RADA 12 INSTALA O COM V LVULA DE MISTURA INSTALA O COM DUAS ZONAS DIRECTAS E DUAS ZONAS MISTURADAS INTRODU O DOS PAR METROS Para utilizar o comando dist ncia CR como no pai nel dist ncia da caldeira e...

Page 58: ...S2 R M SE TA1 SE SI P1 TA2 EXP VM EXP IP TA1 TA2 P2 VM IP EXP EXP INSOL Vers BFT T 14 INSTALA O SOLAR INSTALA O COM DUAS ZONAS MISTURADAS INDEPENDENTES DUAS KIT ZONA MIX C d 8092234 E UM KIT INSOL C d...

Page 59: ...rm stato fumos VD V lvula desviadora M Modulador SM Sonda aquecimento SS Sonda sanitaria TPA Transdutor de press o FLM Flux metro sanit rio TA1 Term stato ambiente Zona 1 TA2 Term stato ambiente Zona...

Page 60: ...dor SM Sonda aquecimento SS Sonda sanitaria TPA Transdutor de press o FLM Flux metro sanit rio TA1 Term stato ambiente Zona 1 TA2 Term stato ambiente Zona 2 ST Sonda temperature solaire CR Comando dis...

Page 61: ...TPA Transdutor de press o TA1 Term stato ambiente Zona 1 TA2 Term stato ambiente Zona 2 SB Sonda fervidor CR Comando dist ncia CR 73 opcional SE Sonda temperatura exterior opcional OP Rel gio program...

Page 62: ...diminui o valor introduzido CONE FUNCIONAMENTO QUEIMADOR E BLOQUEIO CONE NECESSIDADE DE RESET CONE FUN O LIMPA CHAMIN S DIGIT SECUND RIOS A caldeira visualiza o valor da press o do cir cuito valor co...

Page 63: ...ualizzazione codice errore ultima anomalia 15 Contatore accessi parametri installatore es 140 accessi 5 Visualizzazione temperatura sonda fumi 8 Visualizzazione corrente di ionizzazione in A 16 Contat...

Page 64: ...presente su 2 schedino EXP config ZONA MIX 36 Visualizzazione stato flussostato solare rispettivamente ON e OFF 17 Visualiza o volume sanit rio flux metro ex 18 l min ou o estado do flux stato respec...

Page 65: ...auxiliar AUX 1 Al remoto 1 s fervidor 2 B Recircula o 6 Barra luminosa presen a tens o 0 Desactivada 1 1 Activa 0 N o atribu do 7 Atribui o canais CR 73 1 Circuito 1 1 2 Circuito 1 e 2 8 9 1 CR 73 10...

Page 66: ...na compreens o da defini o corrente ou de comportamento an malo ou incompreens vel da caldeira aconselha se restabelecer os valores iniciais dos par metros definindo o PAR49 1 e os PAR1 e PAR2 como es...

Page 67: ...nciona em ambos os servi os Com a sonda sanit rio SS interrompida a caldeira funciona mas n o faz a modula o de pot ncia na fase sanit rio 3 7 ENCENDIDO ELECTR NICO O acendimento e a detec o da chama...

Page 68: ...do na fig 16 3 10 PREVAL NCIA DISPON VEL fig 17 A preval ncia residual para o circuito de aquecimento est representada em fun o do caudal no gr fico da fig 17 A velocidade da bomba modul vel definida...

Page 69: ...2 Por fim aplicar no painel da carca a a etiqueta indicativa do g s para a qual est preparada fornecida no kit NOTA Ao montar os componentes retirados substituir as anilhas do g s e depois da montage...

Page 70: ...r completamente uma tornei ra de gua quente sanit ria Pressionar a tecla Para as regula es lembre se que as rota es no sentido dos ponteiros do rel gio aumentam a press o e as no sentido inverso a dim...

Page 71: ...o do g s Desmonte o env lucro e o bloco queima dores colector de g s Lance um jacto de ar na direc o do interior dos quei madores para a limpeza do p acumula do Limpar o permutador de calor retirando...

Page 72: ...aldei ra da respectiva descarga Colocar um recipiente de recolha sob o fil tro e limp lo eliminando as impurezas e incrusta es calc rias Antes de montar de novo a tampa com o filtro controlar a junta...

Page 73: ...press o indicada pelo transdutor se estabelecer entre 1 e 1 5 bar AP S O ENCHIMENTO FECHAR O MAN PULO GIRANDO O EM SENTIDO HOR RIO Se for necess rio repetir a opera o de abastecimento do circuito aco...

Page 74: ...nda entrada sanit rio Quando a sonda est aberta ou em curto circuito a caldeira perde a fun o solar e no display aparece a ano malia ALL 10 ANOMALIA MODULADOR ALL 11 fig 24 m Anomalia modulador deslig...

Page 75: ...display visualiza se a anomalia ALL 26 Durante tal anomalia a caldeira continua o funcionamento normal ANOMALIA COER NCIA APLICA O SOLARE ALL 27 fig 24 w Quando resulta ligado caldeira o adap tador s...

Page 76: ...O E FUNCIONAMENTO ACENDIMENTO CALDEIRA fig 25 O primeiro acendimento da caldeira deve ser feito pelo pessoal t cnico autorizado Seguidamente caso seja necess rio p r a caldeira em servi o seguir atenc...

Page 77: ...de correc o diversa de um valor de temperatura pro porcional calculado O display apresenta se como indicado na figura 26 a REGULA O DA TEMPERATURA DA GUA SANIT RIA fig 27 Para introduzir a temperatura...

Page 78: ...la do comando para iniciar a caldeira Se anomalia permanece pedir a inter ven o de pessoal t cnico autorizado ALL 07 fig 28 d Pressionar a tecla do comando 2 para iniciar a caldeira Se anomalia perman...

Page 79: ...t of the products of the combustion is unobstructed and has been properly installed Make sure that any shutoff valves are open Make sure that the system is charged with water and is thoroughly vented...

Page 80: ...ELLE EV 25 30 35 BF with electro nic modulation ignition sealed combu stion chamber forced flow MURELLE EV 20 25 BFT only heating with electronic modulation ignition sea led combustion chamber and for...

Page 81: ...U D H W outlet G 1 2 UNI ISO 228 1 DIMENSIONS 25 30 35 L mm 400 450 450 K mm 180 205 205 ATTENTION The BFT version is designed for the connection of a remote boiler to use it as a boiler ONLY FOR HEAT...

Page 82: ...65 10 65 10 65 10 65 D H W flow rate EN 625 l min 10 7 12 7 11 1 13 2 15 3 Continuous D H W flow rate t 30 C l min 10 9 12 9 11 3 13 4 15 5 Minimum D H W flow rate l min 2 4 2 4 2 4 2 4 2 4 D H W pre...

Page 83: ...el 13 3 BAR safety valve 14 Boiler discharge 16 Water pressure transducer 18 D H W flowmeter 19 D H W filter 20 Loading 21 Aqua Guard Filter System 22 Connection plate optional 23 D H W cock optional...

Page 84: ...tion detection electrode 10 Coupling protection 25 30 OF models 25 30 35 BF 20 25 BFT models KEY 1 Control panel 2 Deviator valve 3 Combustion chamber 4 Fan 5 Combustion analysis intakes 6 Negative pr...

Page 85: ...8092234 Antifreeze heaters kit 15 C code 8089806 BF BFT models 2 3 CONNECTING UP SYSTEM To protect the heat system from damaging corrosion incrustation or deposits before installation it is extremely...

Page 86: ...o the indi cations of fig 5 a 2 7 3 Accessories 80 125 fig 6 The 80 125 coaxial duct is supplied on C12 C32 C42 3 1 2 7 6 4 3 2 8 x y x y max 5 0 m per vers 20 x y max 3 5 m per vers 25 x y max 3 0 m...

Page 87: ...e burner In these cases a condensation system on the pipes must be provided for If the pipe passes through inflammable C12 C32 C42 2 7 6 4 1 2 min 4 m max 7 m 8 x y x y min 3 5 m max 6 m 25 x y min 3...

Page 88: ...50 Total head loss 2 25 3 40 5 65 mmH2O With this total head loss remove the segments from No 1 to No 7 from diaphragm in the intake pipe 1 2 3 4 6 165 110 165 K 80 80 100 92 Fig 8 Fig 8 a Fig 7 KEY 1...

Page 89: ...0 elbows MF code 8077408 3a Extension L 1000 n 6 code 8077309 3b Insulated extension L 1000 code 8077306 3c Extension L 500 n 6 code 8077308 3d Extension L 135 code 8077304 4 Outlet terminal code 8089...

Page 90: ...RMINALS fig 11 The outlet terminals for forced draught systems may be located on the outer walls of the building Table 2 shows approximate non binding minimum distances to be met for a building of the...

Page 91: ...to 1 PAR 10 1 2 11 4 External sensor connection The boiler is designed for connection to an external temperature sensor supplied on request code 8094101 which can auto matically regulate the temperat...

Page 92: ...AT AND EXTERNAL SENSOR Code 8094101 3 BASIC SYSTEM MULTI ZONE SYSTEM WITH PUMP ROOM THERMOSTAT AND EXTERNAL SENSOR Code 8094101 4 BASIC SYSTEM MULTI ZONE SYSTEM WITH VALVE ROOM THERMOSTAT REMOTE CONTR...

Page 93: ...nd changing the value with the keys and SI R M SE TA1 TA2 TA2 SE TA P2 RL RL1 RL2 P1 P CR CR 5 BASIC SYSTEM MULTI ZONE SYSTEM WITH VALVE ROOM THERMOSTAT REMOTE CONTROL CR 73 Code 8092226 AND EXTERNAL...

Page 94: ...o the entrance TA1 R M SE TA2 TA1 SE TA1 SI RL2 P2 P1 PB RL1 BOLLITORE PB SB SB R M SE CT2 TA1 SE CT1 SI RL2 P2 P1 TA2 RL1 ZONA GIORNO 70 C ZONA NOTTE 50 C 8 SYSTEM WITH DOUBLE TEMPERATURE OUTPUT MULT...

Page 95: ...ZONE AND ONE MIXED ZONE 12 SYSTEM WITH MIXER VALVE SYSTEM WITH TWO DIRECT ZONES AND TWO MIXED ZONES PARAMETERS SETTINGS To use the remote control CR as remote control panel for the boiler rather than...

Page 96: ...S2 R M SE TA1 SE SI P1 TA2 EXP VM EXP IP TA1 TA2 P2 VM IP EXP EXP INSOL Vers BFT T 14 SYSTEM SOLAR SYSTEM WITH TWO MIXED ZONES INDEPENDENT TWO KITS ZONA MIX Code 8092234 AND ONE KIT SOLAR INSOL Code...

Page 97: ...Fumes thermostat VD Deviator valve M Modulator SM Heating sensor SS D H W sensor TPA Pressure transducer FLM D H W flowmeter TA 1 Zone 1 environment thermostat TA 2 Zone 2 environment thermostat ST S...

Page 98: ...ing sensor SS D H W sensor TPA Pressure transducer FLM D H W flowmeter TA 1 Zone 1 environment thermostat TA 2 Zone 2 environment thermostat ST Solar heat sensor CR Remote control CR 73 optional SE Ex...

Page 99: ...TA 1 Zone 1 environment thermostat TA 2 Zone 2 environment thermostat SB D H W tank sensor CR Remote control CR 73 optional SE External sensor optional OP Programming clock optional EXP Expansion car...

Page 100: ...the set value increases or decrea ses BURNER FUNCTIONING AND BLOCK ICON DESCRIPTION OF DISPLAY ICONS CHIMNEY SWEEP ICON SECONDARY DIGITS The boiler visualises the value of the pressure of the system...

Page 101: ...dice errore ultima anomalia 15 Contatore accessi parametri installatore es 140 accessi 5 Visualizzazione temperatura sonda fumi 8 Visualizzazione corrente di ionizzazione in A 16 Contatore accessi par...

Page 102: ...software presente su schedino EXP config ZONA MIX 92 Versione software presente su 2 schedino EXP config ZONA MIX 36 Visualizzazione stato flussostato solare rispettivamente ON e OFF 17 Visualisation...

Page 103: ...AUX 1 Remote supply 1 D H W tank 2 Recirculation pump 6 Luminous bar indicating presence 0 Disabled 1 of voltage 1 Enabled 0 Not assigned 7 Allocation of CR73 channels 1 Circuit 1 1 2 Circuits 1 and 2...

Page 104: ...in case of an anomalous or incomprehensible conduct of the boiler we suggest to restore the initial values of the parameters setting PAR 49 1 and the PAR 1 and PAR 2 as specified at point 3 3 1 BOILE...

Page 105: ...unctions but will not made the power modulations for the D H W 3 7 ELECTRONIC IGNITION Ignition and flame detection is controlled by a single electrode on the burner which gua rantees reaction in the...

Page 106: ...is measured by a differential pressure gauge connected as indicated in fig 16 3 10 HEAD AVAILABLE TO SYSTEM fig 17 Residual head for the heating system is shown as a function of rate of flow in the g...

Page 107: ...own with the keys and The display pane will show the values of the parameter PAR 1 If for example the boiler in question is a 25 BF fuelled by methane the following setting SET 2 will appear To change...

Page 108: ...ile the sanitary water tap is on with the water running Lock the nut 3 in place turn the screw nut 2 to the minimum pressu re indicated in Table 4 Press the keys and while keeping the hot sanitary wat...

Page 109: ...the test the hot water faucets must remain open If the key and are pressed during the 15 minutes of the chimney sweep func tion the boiler will be brought respectively to maximum and minimum power Th...

Page 110: ...f the load procedure has to be repeated several times it is advisable to check that the seal of the heating circuit is intact check that there are no leaks HIGH WATER PRESSURE ANOMALY ALARM 03 fig 24...

Page 111: ...ODULATOR ANOMALY ALARM 11 fig 24 m The modulator is not connected When during functioning the boiler detects zero current to the modulator the display will show anomaly ALL 11 The boiler will function...

Page 112: ...obe is open or short circuited on the display the anomaly ALL 26 appears During this anomaly the boiler continues to function normally SOLAR APPLICATION COHERENCE ANOMALY ALL 27 fig 24 w When it resul...

Page 113: ...gain adhere strictly to the fol lowing instructions open the gas tap to allow the flow of the fuel Move the main switch of the system to ON When fuel is fed to the boiler a sequence of checks will be...

Page 114: ...f the anomaly persists request the intervention of qualified technical per sonnel ALL 02 fig 28 a If the water pressure detected is lower than 0 5 bar the boiler will stop and the display will show AL...

Page 115: ......

Page 116: ...Fonderie Sime S p A Via Garbo 27 37045 Legnago Vr Tel 39 0442 631111 Fax 39 0442 631292 www sime it Documentation Dpt Fonderie Sime S p A...

Reviews: