81
ES
PT
ENG
3.2
ACCESS TO INSTALLER'S
PARAMETERS
For access to the installer's parameters,
press simultaneously the keys of boiler
panel (
and
) for 5 seconds.
The red LED flashes and the display shows:
The parameters can be scrolled with
or
.
To enter the parameter press
or
.
The value set
flashes
, the display shows:
Proceed as follows to change the set value:
- set the new value using
or
.
- confirm the set value using
or
.
Press
to exit the parameters section.
The display is shown automatically after 5
minutes.
The parameters section contains the
alarms log, info and meters (display only).
3.2.1
Replacing the board or
RESETTING parameters
If the electronic board is replaced or reset,
it is necessary to configure PAR 01 and
PAR 02 by associating the following values
to each type of boiler to be able to restart
the boiler:
NOTE: the boiler panel has a label with
the values that have to be set for PAR 01
and PAR 02 (fig. 21).
BOILER
GAS
MODELS
PAR 1
METHANE
25
01
BF
(G20)
30
02
LPG
25
03
(G30/G31)
30
04
METHANE
25
05
OF
(G20)
30
06
LPG
25
07
(G30/G31)
30
08
BOILER
PAR 2
OF/BF
09
OF/BF
10
combined
with sun-panel system
OF/BF
13
with automatic filling
OF/BF
14
combined
with sun-panel system
and with automatic filling
PARAMETERS INSTALLER
FAST CONFIGURATION
PAR DESCRIPTION
RANGE
UNIT OF
INC/DEC
DEFAULT
MEASUREMENT
UNIT
SETTING
01 Combustion configuration
-- = ND
=
=
“--”
1 ... 8
02 Hydraulic configuration
-- = ND
=
=
“--”
1 ... 22
03 Disabling of voltage presence LED
0 = Disabled
=
=
01
1 = Enabled
04 Correction of external probe values
-5 ... 05
°C
1
00
05 Timer block of the keys
-- = Disabled
Min.
1
15
1 ... 99
D.H.W. - HEATING
PAR DESCRIPTION
RANGE
UNIT OF
INC/DEC
DEFAULT
MEASUREMENT
UNIT
SETTING
10
Boiler antifreeze
0 ... 10
°C
1
03
11
External sensor antifreeze
-- = Disabled
°C
1
- 2
- 9 ... 05
12
Climatic curve setting
03 ... 40
=
1
20
13
Minimum temperature heating
40 ... PAR 14
°C
1
40
14
Maximum temperature heating
PAR 13 ... 80
°C
1
80
15
Maximum power heating
30 ... 99
%
1
99
16
Post-circulation time
0 ... 99
10 sec.
1
03
17
Pump heating activation delay
0 ... 99
10 sec.
1
01
18
Re-ignition delay
0 ... 10
Min.
1
03
19
Modulation D.H.W. flowmeter
-- = Disabled
=
=
01
1 = Enabled
29
Anti-legionella (only D.H.W. tank)
-- = Disabled
°C
1
“--”
50 ... 80
PARAMETERS RE-SET
PAR DESCRIPTION
RANGE
UNIT OF
INC/DEC
DEFAULT
MEASUREMENT
UNIT
SETTING
49 * Reset default parameters
-- , 1
=
=
=
(PAR 01 - PAR 02 equal “---”)
* If the current setting is difficult to understand or anomalous behaviour or if it is difficult to understand
the boiler, it is advised to restore the initial parameter values by setting PAR 49 = 1 and PAR 1 and
PAR 2 as specified in point 3.2.1.
ALARMS (visualization)
PAR DESCRIPTION
RANGE
UNIT OF
INC/DEC
DEFAULT
MEASUREMENT
UNIT
SETTING
A0
Last code anomaly appearance
=
=
=
=
A1
Code anomaly previously appearance
=
=
=
=
A2
Code anomaly previously appearance
=
=
=
=
A3
Code anomaly previously appearance
=
=
=
=
A4
Code anomaly previously appearance
=
=
=
=
A5
Code anomaly previously appearance
=
=
=
=
A6
Code anomaly previously appearance
=
=
=
=
A7
Code anomaly previously appearance
=
=
=
=
A8
Code anomaly previously appearance
=
=
=
=
A9
Code anomaly previously appearance
=
=
=
=
INFO (visualization)
PAR DESCRIPTION
RANGE
UNIT OF
INC/DEC
DEFAULT
MEASUREMENT
UNIT
SETTING
i0
External sensor temperature
-9 ... 99
°C
1
=
i1
C.H. 1 sensor temperature
-9 ... 99
°C
1
=
i2
C.H. 2 sensor temperature
-9 ... 99
°C
1
=
i3
D.H.W. sensor temperature
-9 ... 99
°C
1
=
i4
Auxiliary sensor AUX temperature
-9 ... 99
°C
1
=
i5
Set of effective heating temperature
PAR 13 ... PAR 14
°C
1
=
i6
Level survey flame
00 ... 99
%
1
=
i7
Current to the modulator
00 ... 17
10 mA
1
=
i8
Flow rate
D.H.W. flow meter
00 ... 99
l/min
1
=
COUNTERS (visualization)
PAR DESCRIPTION
RANGE
UNIT OF
INC/DEC
DEFAULT
MEASUREMENT
UNIT
SETTING
c0 Number hours of operation of the burner
00 ... 99
h x 100
0,1
from 0,0 to 9,9 00
1
from 10 to 99
c1 Number of ignitions of the burner
00 ... 99
x 1000
0,1
from 0,0 to 9,9 00
1
from 10 to 99
c2 Number total of the anomalies
00 ... 99
x 1
1
00
c3
Number approached the parameters installator 00 ... 99
x 1
1
00
c4
Number approached the parameters OEM
00 ... 99
x 1
1
00