1.6
COMBUSTION CHAMBER (fig. 3)
The combustion chamber is of the
straight flow type and complies with
standard EN 303-3 appendix E.
The dimensions are shown in fig. 3.
1.7
COMPATIBLE BURNERS
(
EN 267)
In general, the oil burner that is compati-
ble with the boiler should use spray
of the semi solid type.
Sections 1.7.1 shows the matching table
of the burners with the boilers have been
tested with.
L
270
280
Fig. 3
L
Volumen
mm
dm
3
Estelle HE 3 ErP
305
17.5
Estelle HE 4 ErP
405
24.0
Estelle HE 5 ErP
505
30.5
Estelle HE 6 ErP
605
37.0
Estelle HE 7 ErP
705
43.5
36
1.5
FUNCTIONAL DIAGRAM (fig. 2/a)
1
2
3
M
R
KEY
1 Boiler
2 Stainless steel condenser
3 Condensate drain tap
M C.H. flow
R C.H. return
Fig. 2/a
1.7.1 Permanent feeding burners
Model
Code
Nozzle
Atomising
Pump
Class
Adsorbed power
Type
ø
angle
pressure
NOx
consumption
bar
W
Estelle HE 3 ErP
SIME MACK 3
8099000
DELAVAN
0,55
60°S
12,5
1
155
Estelle HE 4 ErP
SIME MACK 4
8099010
DELAVAN
0,75
60°W
11,0
1
163
Estelle HE 5 ErP
SIME MACK 5
8099030
DELAVAN
0,85
60°W
13,0
1
163
Estelle HE 6 ErP
SIME MACK 6
8099050
DELAVAN
1,00
60°W
12,0
1
151
Estelle HE 7 ErP
SIME MACK 6
8099050
DELAVAN
1,25
60°W
12,0
1
151
Estelle HE 3 ErP
FBR G0 SR LX TXC 8099124
DANFOSS
0,50
45°H
12,5
3
120
Estelle HE 4 ErP
FBR G0 SR LX TXC 8099125
DANFOSS
0,65
45°H
12,5
3
120
Estelle HE 5 ErP
FBR G1 SR LX
8099126
DANFOSS
0,75
45°H
12,0
3
220
Estelle HE 6 ErP
FBR G1 SR LX
8099126
DANFOSS
1,00
45°H
13,0
3
220
Estelle HE 7 ErP
FBR G2.22 R LX
8099127
DANFOSS
1,25
45°H
12,0
3
140
Summary of Contents for ESTELLE HE 3 ErP
Page 98: ...98 NOTE ...
Page 99: ......