97
EN
Information requirements for boiler space heaters, boiler combination heaters
Model(s):
ESTELLE HE 3 ErP
Condensing boiler:
Yes
Low-temperature boiler:
Yes
B11 boiler:
No
Cogeneration space heater:
No
Equipped with a supplementary heater:
No
Combination heater:
Yes
Item
Symbol
Value
Unit
Item
Symbol
Value
Unit
Nominal heat output for space heating
P
n
25
kW
Seasonal space heating energy efficiency
η
s
91
%
For boiler space heaters and boiler combination heaters:
useful heat output
For boiler space heaters and boiler combination heaters:
useful efficiency
At nominal heat output and high-
temperature regime
a
P
4
25,1
kW
At nominal heat output and high-
temperature regime (*)
η
4
90,1
%
At 30% of nominal heat output and
low-temperature regime
b
P
1
7,5
kW
At 30% of nominal heat output and
low-temperature regime (*)
η
1
97,0
%
Auxiliary electricity consumption
Other items
At full load
el
max
0,168
kW
Standby heat loss
Pstby
0,019
kW
At part load
el
min
0,050
kW
Ignition burner power consumption
Pign
0
kW
In standby mode
PSB
0,002
kW
Emissions of nitrogen oxides
NOx
-
mg/
kWh
For combination heaters:
Declared load profile
-
Water heating energy efficiency
η
wh
-
%
Daily electricity consumption
Qelec
-
kWh
Daily fuel consumption
Qfuel
-
kWh
Contact details
Fonderie Sime S.p.A. Via Garbo 27, 37045 Legnago (VR) ITALIA
a. High-temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
b. Low-temperature regime means for condensing boilers 30°C, for low-temperature boilers 37°C and for other heaters 50°C return
temperature.
(*) The yield data have been calculated using the higher heating value.