1.5 

COMPATIBLE BURNERS

 

(

 EN 267)

In general, the oil burner that is compati-
ble with the boiler should use spray
of  the  semi  solid  type.  Sections  1.5.2 
shows the matching table  of the burners 
with the boilers have been tested with.

ATTENTION:
Water  heater  with  Nominal  Power  Pn 
›70kW:  It  is  possible  to  use  burners  that 
are not on the list but have the same cha-
racteristics,  as  long  as  they  are  confor-
ming to the standard/s, reference techni-
ques and suitable field of work. 

Water  heaters  with  Nominal  Power  Pn 
‹70kW:  It  is  possible  to  use  burners  that 
are not on the list but have the same cha-
racteristics,  as  long  as  they  are  confor-
ming to the standard/s, reference techni-
ques.

When  choosing  the  burner,  pay  attention 
to  the  max  electrical  power  absorbed  by 
the burner at 30% of the load and in stand-
by  that  should  be  the  same  or  less  that 
those indicated in the water heater tech-
nical data.

1.5.1  Burners assembly (fig. 4)

The boiler door details is shown in figure 
3/a for burner mounting.
The burners must be regulated such that 
the  CO

2

  value  is  that  indicated  in  point 

1.3, with a tolerance of ± 5%.

28

Fig. 4

C

A

B

2R HE 

C

 

mm  mm 

ø

6 ErP 

130  170 

M8

7 ErP 

130  170 

M8

8 ErP 

130  170 

M8

9 ErP 

130  170 

M8

10 ErP 

160  190  M10

11 ErP 

160  190  M10

12 ErP 

160  190  M10

13 ErP 

160  190  M10

1.5.2  Permanent feeding burners

 

Model 

Code 

  Nozzle 

 

Atomising 

Pump 

Class 

Adsorbed power

 

 

 

Type 

  

ø 

angle 

pressure 

NOx 

consumption

 

 

 

 

 

 

  

 

bar 

 

W

2R HE 6 ErP 

SIME MACK 6 

8099050 

DELEVAN   

1,65 

60°B 

12,0 

151

2R HE 7 ErP 

SIME MACK 6 

8099050 

DELEVAN   

1,75 

60°B 

11,5 

151

2R HE 8 ErP 

SIME MACK 7 

8099060 

DELEVAN   

2,00 

60°B 

12,0 

300

2R HE 9 ErP 

SIME MACK 7 

8099060 

DELEVAN   

2,50 

60°B 

12,0 

300

2R HE 10 ErP 

SIME MACK 7 

8099060 

DELEVAN   

3,00 

60°B 

12,0 

300

2R HE 11 ErP 

FBR G X4.22 

8099128 

DELEVAN   

3,50 

60°B 

12,6 

263

2R HE 12 ErP 

FBR G X4.22 

8099128 

DELEVAN   

3,50 

60°B 

12,6 

263

2R HE 13 ErP 

FBR G X4.22 

8099128 

DELEVAN   

3,50 

60°B 

12,6 

263

ATTENTION: Use FBR compatible burners for operation with dual-level burner.

Summary of Contents for 2R HE 10 ErP

Page 1: ...TIONS ORIGINALES ORIGINALANLEITUNG ORIGINALANWEISUNGEN INSTRUCȚIUNI ORIGINALE ΑΡΧΙΚΕΣ ΟΔΗΓΙΕΣ Gentile Cliente metta in funzione la sua nuova caldaia entro 30gg dalla data di installazione da personale professionalmente qualificato Potrà così beneficiare sia della garanzia legale sia della garanzia convenzionale Sime che trova alla fine di questo manuale NL DE RO GR IT ES ENG FR ...

Page 2: ...2 5 ELECTRICAL CONNECTION 3 USE AND MAINTENANCE 3 1 COMMISSIONING THE BOILER 33 3 2 LIGHTING AND OPERATION 3 3 REGULAR CLEANING 34 3 4 FROST POTECTION 35 3 5 POWER CABLE 3 6 DISPOSAL OF THE EQUIPMENT 2R HE ErP ENGLISH CONFORMITY Our Company declares that 2R HE ErP boilers comply with the essential requirements of the following directives Boiler Efficiency Directive 92 42 EC Ecodesign Directive 200...

Page 3: ... INPUT MAX HEAT OUTPUT MAX MAX OPERATING PRESSURE CONTENTS D H W HEAT INPUT MAX D H W MAX OPERATING PRESSURE D H W D H W FLOW RATE POWER SUPPLY MAX POWER ABSORBED TYPE CODE DIRECTIVE OF REFERENCE PIN NUMBER MAX OPERATING PRESSURE MAX OPERATING PRESSURE D H W 1 2 1 Technical data plate fig 2 Fig 2 2R HE 6 ErP 7 ErP 8 ErP 9 ErP 10 ErP 11 ErP 12 ErP 13 ErP L Depth mm 1232 1355 1478 1601 1724 1847 197...

Page 4: ...392 4 392 Water content l 74 2 84 3 94 9 105 5 116 1 126 7 137 4 147 9 Smokes loss of head mbar kPa 0 35 0 034 0 45 0 044 0 50 0 049 0 55 0 054 0 65 0 064 0 75 0 073 0 85 0 083 0 90 0 088 Combustion chamber pressure mbar kPa 0 42 0 041 0 55 0 054 0 65 0 064 0 75 0 073 0 85 0 083 1 10 0 108 1 49 0 146 1 56 0 153 Suggested chimney depression mbar kPa 0 15 0 015 0 15 0 015 0 15 0 015 0 15 0 015 0 15 ...

Page 5: ...ta 1 5 1 Burners assembly fig 4 The boiler door details is shown in figure 3 a for burner mounting The burners must be regulated such that the CO2 value is that indicated in point 1 3 with a tolerance of 5 28 Fig 4 C A B 2R HE A B C mm mm ø 6 ErP 130 170 M8 7 ErP 130 170 M8 8 ErP 130 170 M8 9 ErP 130 170 M8 10 ErP 160 190 M10 11 ErP 160 190 M10 12 ErP 160 190 M10 13 ErP 160 190 M10 1 5 2 Permanent...

Page 6: ... rear insulation panel 4 fasten the lower cross beam 3 to the cast iron body with two hex head screws fasten the sides 5 6 to the supports 1 with four self tapping screws and lock them in the back using nuts inser ted on the tie rods install the upper rear panel 7 8 with the four self tapping screws supplied fasten the control panel 9 to the corners 2 with the four self tapping screws supplied unw...

Page 7: ...30 4 x 4 x 5 x 4 x 2 x 13 17 16 18 19 6 x 20 14 15 15 7 8 7 8 13 15 15 20 19 5 6 11 21 21 4 Fig 5 b ...

Page 8: ...pan sion vessel with a capacity of 8 litres and a maximum pressure of 8 bar 784 kPa The tank should be of the membrane type made of natural rubber caou tchouc which is suitable for foods 2 4 CONNECTING UP FLUE The flue is of fundamental importance for the proper operation of the boiler if not installed in compliance with the stand ards starting the boiler will be difficult and there will be a cons...

Page 9: ...rner optional B1 Permanent feeding dual level burner optional B2 Direct feeding Burner TA Room stat OP Programmer s clock NO TE When a room stat TA is to be fitted remove the link between terminal 4 and 5 on the connector plug To connect the programmer s clock OP remove the link between terminals 5 and 6 NOTE The brown capped off cable and black capped off cable has to be exclusively used in case ...

Page 10: ...to confirm 3 USE AND MAINTENANCE WARNINGS In case of failure or malfunction of the equipment contact authorised technical staff For safety reasons the User cannot access the internal parts of the appliance All operations involving the removal of protections or otherwise the access to dan gerous parts of the appliance must be performed by qualified personnel The appliance can be used by children un...

Page 11: ...less than 1 bar 98 kPa reset the system 3 2 5 Turnig OFF boiler fig 7 To temporarily turn off the boiler turn off the electricity supply by pressing the main switch The following operations must be carried out if the plant will not be in use for a lengthy period of time position the main switch of the plant on off turn the fuel and water taps of the cen tral heating plant off empty the central hea...

Page 12: ...n the appliance and the relevant list of actions required A working fault in most cases provo cates the lock out signal onto the con trol panel of the control box When this light turns on the burner can operate again only after the reset button has been pressed if this has been done and a regular ignition occurs it means the failure can be defined momentary and not dangerous On the contrary if the...

Page 13: ... of the flue ducts door combustion chamber smoke ducts flue washers Control the quality of the fuel Frequent intervention of the boiler shutoff valve Control the presence of air in the system the function of the circulation pumps Check the load pressure of the appli ance the efficiency of the expansion tanks and the valve calibration 3 4 FROST PROTECTION In the event of frost ensure that the centr...

Page 14: ...Fonderie Sime S p A Via Garbo 27 37045 Legnago Vr Tel 39 0442 631111 Fax 39 0442 631292 www sime it Documentation Dpt Fonderie Sime S p A ...

Reviews: