background image

3126

4

3.2 BURNER ASSEMBLY 

 

In case of 

CF 

applications, the burner shall not operate without pro-

tection 

(A)

 of the suction inlet.

FOR CORRECT BF APPLICATION, THE BURNER MUST BE
INSTALLED ON AN APPROPRIATE BF BOILER.

In case of 

BF 

applications an optional snorkel and gasket are availa-

ble replacing 

(A)

 with 

(B)

. This item can be supplied separately.

The combustion air supply is through a flexible or rigid pipe connect-
ed to the air intake.
Consequently, you must comply with the following requirements and
instructions:

The combustion air intake tube must be:
- fastened securely to the burner;
- made of a suitable material, with temperature characteristics in

the range - 30 °C to 80 °C;

- in compliance with all requirements of applicable regulations in force in the country of destination.

The intake-tube / burner system must not allow a loss of over 2 m

3

/h at 0.5 mbar:

for instance, the above requirements will be met if you use flues for pressure exhaust of flue gases (the
condensation kind).

Make sure the air intake tube’s inlet is positioned so that it is not likely to be obstructed by foreign matter
and, where necessary, use suitable screens.

The temperature of the incoming air must not exceed 40 °C;

The inside diameter of the hose must be at least 80 mm.

The intake tube can be up to 6 metres in length.

Warning

: length is reduced if there are bends in the intake section.

For instance, using a tube with a smooth inside surface, you must allow for the following losses:
- for each 45° bend, tube length is reduced by 0.5 m;
- for each 90° bend, tube length is reduced by 0.8 m.

BURNER INSTALLATION MUST COMPLY WITH ONE OF THE INSTALLATIONS ILLUSTRATED IN THE
FIGURES BELOW.

Under no circumstances should the air’s entry in the hose intake area be obstructed.

The hose must not be blocked in any way or feature a shutting device (valves, membranes etc.).

Coaxial tubes must not be installed for any reason.

D5884

A

B

D5883

CF APPLICATION

BF APPLICATION

ATTENTION

S7851

S7853

S7876

Summary of Contents for 20096000

Page 1: ...2903126 5 12 2014 Installation use and maintenance instructions Light oil burners One stage operation CODE MODEL TYPE 3513687 SIME FUEL 30 DT BFX 744T3R 20096000 SIME FUEL 30 DT BFX 744T3R GB...

Page 2: ......

Page 3: ...ems 5 3 5 Electrical wiring 6 4 WORKING 7 4 1 Combustion adjustment 7 4 2 Nozzles recommended 7 4 3 Pump pressure 7 4 4 Electrodes setting 7 4 5 Air damper adjustment 8 4 6 Fuel heating 8 4 7 Burner s...

Page 4: ...ght oil viscosity 4 6 mm2 s at 20 C Hi 11 86 kWh kg Electrical supply Single phase 50Hz 230V 10 Motor Run current 0 85A 2700 rpm 283 rad s Capacitor 4 5 F Ignition transformer Secondary 8 kV 25 mA Pum...

Page 5: ...ould compromise the correct working of the appliance Installations 4 and 5 are forbidden for safety reasons 3 1 BOILER FIXING Put on the flange 1 the screw and two nuts see fig 2 Fix the flange 1 to t...

Page 6: ...e requirements will be met if you use flues for pressure exhaust of flue gases the condensation kind Make sure the air intake tube s inlet is positioned so that it is not likely to be obstructed by fo...

Page 7: ...mm 0 5 1 1 5 2 10 20 40 60 20 40 80 100 On the systems in fig 6 and 7 start the burner and wait for the priming Should lock out occur prior to the arrival of the fuel await at least 20 seconds before...

Page 8: ...nd remove all components Remove the coil 3 Loosen the two screws 4 Move a little the control box and remove the high voltage leads E9151 4 4 3 1 2 Fig 8 Burner earth Safety thermostat ATTENTION Do not...

Page 9: ...RIED OUT IN THE FACTORY 4 2 NOZZLES RECOMMENDED Delavan type W Steinen type Q Danfoss type S Angle 60 In most cases 80 In case of flame detachment during ignitions at low temperatures 4 3 PUMP PRESSUR...

Page 10: ...k the second ary air damper B SECONDARY AIR DAMPER B fig 11 The purpose of this damper is to perform a fine tun ing of the inlet air Tuning of this device is possible acting of the screw 3 4 6 FUEL HE...

Page 11: ...heck that there are not obstructions or dents in the supply or return oil pipes Clean the filter in the oil suction line and in the pump Clean the photoresistance 9 fig 1 page 1 Check for correct fuel...

Page 12: ...or due to the intervention of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner will not start when the limit thermostat closes Lack of electrical supply Check presence of voltage in th...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...Fonderie Sime S p A via Garbo 27 37045 Legnago Vr Italy Tel 39 0442 631111 Export Division fax number 39 0442 631293 Sime Service fax number 39 0442 631292...

Reviews: