background image

3126

10

6.

FAULTS / SOLUTIONS

Here below you can find some causes and the possible solutions for some problems that could cause a
failure to start or a bad working of the burner.
A  fault usually makes  the  lock-out  lamp  light  which  is  situated  inside the reset button of the control box
(3, fig. 1, page 1).
When lock out lamp lights the burner will attempt to light only after pushing the reset button. After this if the
burner functions correctly, the lock-out can be attributed to a temporary fault.
If however the lock out continues the cause must be determined and the solution found. 

WARNING

The manufacturer cannot accept responsibility for any damage to persons, animals or property due to error
in installation or in the burner adjustment, or due to improper or unreasonable use or non observance of the
technical instruction enclosed with the burner, or due to the intervention of unqualified personnel.

FAULTS

POSSIBLE CAUSES

SOLUTION

The burner will not
start when the limit
thermostat closes.

Lack of electrical supply.

Check presence of voltage in the 
L - N clamps of the control box.

Check the conditions of the fuses.

Check that safety thermostat limit is not 
lock out.

The photoresistance sees false light.

Eliminate the light.

Resistance or start thermostats are 
faulty.

Replace them.

The connections in the control box 
are wrongly inserted.

Check and connect completely all the
plugs.

Burner runs normal-
ly in the prepurge
and ignition cycle
and locks out after 5
seconds ca.

The photoresistance is dirty.

Clear it.

The photoresistance is defective.

Change it.

Flame moves away or fails.

Check pressure and output of the fuel.

Check air output.

Change nozzle.

Check the coil of solenoid valve.

Burner starts with an
ignition delay.

The ignition electrodes are wrongly 
positioned.

Adjust them according to the
instructions of this manual.

Air output is too high.

Set the air output.

Nozzle dirty or worn.

Replace it.

Summary of Contents for 20096000

Page 1: ...2903126 5 12 2014 Installation use and maintenance instructions Light oil burners One stage operation CODE MODEL TYPE 3513687 SIME FUEL 30 DT BFX 744T3R 20096000 SIME FUEL 30 DT BFX 744T3R GB...

Page 2: ......

Page 3: ...ems 5 3 5 Electrical wiring 6 4 WORKING 7 4 1 Combustion adjustment 7 4 2 Nozzles recommended 7 4 3 Pump pressure 7 4 4 Electrodes setting 7 4 5 Air damper adjustment 8 4 6 Fuel heating 8 4 7 Burner s...

Page 4: ...ght oil viscosity 4 6 mm2 s at 20 C Hi 11 86 kWh kg Electrical supply Single phase 50Hz 230V 10 Motor Run current 0 85A 2700 rpm 283 rad s Capacitor 4 5 F Ignition transformer Secondary 8 kV 25 mA Pum...

Page 5: ...ould compromise the correct working of the appliance Installations 4 and 5 are forbidden for safety reasons 3 1 BOILER FIXING Put on the flange 1 the screw and two nuts see fig 2 Fix the flange 1 to t...

Page 6: ...e requirements will be met if you use flues for pressure exhaust of flue gases the condensation kind Make sure the air intake tube s inlet is positioned so that it is not likely to be obstructed by fo...

Page 7: ...mm 0 5 1 1 5 2 10 20 40 60 20 40 80 100 On the systems in fig 6 and 7 start the burner and wait for the priming Should lock out occur prior to the arrival of the fuel await at least 20 seconds before...

Page 8: ...nd remove all components Remove the coil 3 Loosen the two screws 4 Move a little the control box and remove the high voltage leads E9151 4 4 3 1 2 Fig 8 Burner earth Safety thermostat ATTENTION Do not...

Page 9: ...RIED OUT IN THE FACTORY 4 2 NOZZLES RECOMMENDED Delavan type W Steinen type Q Danfoss type S Angle 60 In most cases 80 In case of flame detachment during ignitions at low temperatures 4 3 PUMP PRESSUR...

Page 10: ...k the second ary air damper B SECONDARY AIR DAMPER B fig 11 The purpose of this damper is to perform a fine tun ing of the inlet air Tuning of this device is possible acting of the screw 3 4 6 FUEL HE...

Page 11: ...heck that there are not obstructions or dents in the supply or return oil pipes Clean the filter in the oil suction line and in the pump Clean the photoresistance 9 fig 1 page 1 Check for correct fuel...

Page 12: ...or due to the intervention of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner will not start when the limit thermostat closes Lack of electrical supply Check presence of voltage in th...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...Fonderie Sime S p A via Garbo 27 37045 Legnago Vr Italy Tel 39 0442 631111 Export Division fax number 39 0442 631293 Sime Service fax number 39 0442 631292...

Reviews: