
Installation
17
users manual inverter SE3.3Ni - SE3.8Ni - SE4.6Ni
Fig. 2.3.1.2 Assembly of the AC cable and the AC connector
CAUTION!
To ensure that the total impedance of the grid plus the interconnection AC power cable shall be less than 1.25 .
1. The AC connector is suitable for cables with a cross-section of up to 4 mm
2
.
2. Connect the cable GND to the screw labeled of the AC connector
3. Connect the cable N to the screw labeled N of the AC connector.
4. Connect the cable L to the screw labeled L of the AC connector.
5. Tighten the screws with a torque of 0.9Nm.
WARNING!
Each connection to a SE inverter must be installed with a separate circuit breaker with 25A type B. No other appliances may be
connected to the circuit breaker.
6. Reconfirm that all connections have been performed properly as described above and all screws are properly tightened.
7. Plug the AC connector into the AC terminal to complete AC cable connection for the inverter.
Summary of Contents for SE3.3Ni
Page 1: ...nverters...
Page 8: ...ror Messages n ations on 44 44 47 50 50 51 52 53...
Page 26: ...25 3 7 Assembly of the Waterproof RJ 45 plug...
Page 28: ...27 2 4 2 Parallel configuration of inverter incorrect 7...
Page 56: ...55...
Page 57: ...Notes user s manual inverter SE3 3Ni SE3 8Ni SE4 6Ni...
Page 58: ......