151165
5-1
Section 5
System Configuration
To configure the SK-2224 system, set the DIP switch that controls the option you want to
select. The following chart shows how to program the DIP switches that control system, zone,
and notification appliance operation. Refer to Figure 3-1 for location of the DIP switches.
Important!
When you change a DIP switch, be sure to power down the panel. DIP switch changes will be
recognized on power up only. Some switches are unused and are not referred to in this chart.
Leave all unused switches in their factory-programmed OFF position.
Table 5-1: System Configuration
To Enable
For Zone 1 (DIP 1) For Zone 2 (DIP 1)
DIP Position
Enhanced mode (DIP switch ON). Use when both pull
stations and detectors will be used in the same zone.
Normal mode (DIP switch OFF). Use when 4-wire smoke
detectors and smoke verification are used in the same zone.
SW1
SW6
ON = Enhanced
OFF = Normal
Alarm verification
Note: Do not use with smoke detectors that have verifica-
tion built-in.
SW 2
SW 7
ON = Verification zone
OFF = No verification
Zone Type
Fire alarm
SW 3
SW8
OFF
Supervisory
SW 3
SW8
ON
Alarm delay options
Note: Alarm delay options are to be
used with water flow devices
only. If the device has a built-
in delay time, the total delay
time (device delay + pro-
grammed delay) can not ex-
ceed 120 seconds.
No delay
SW4
SW5
SW9
SW10
OFF
OFF
30 second delay
SW4
SW5
SW9
SW10
ON
OFF
60 second delay
SW4
SW5
SW9
SW10
OFF
ON
90 second delay
SW4
SW5
SW9
SW10
ON
ON
To Enable
For NAC 1 (DIP 2)
For NAC 2 (DIP 2)
DIP Position
Silencing
SW 1
SW 3
ON = Can be silenced
OFF = No silence
ANSI pattern
SW 2
SW 4
ON = ANSI
Off = Steady
Summary of Contents for SK-2224
Page 1: ...Fire Control Panel Part Number 151051F 02 02 SK 2224 Installation and Operation Manual ...
Page 5: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 1 2 151165 ...
Page 7: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 2 2 151165 ...
Page 17: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 3 10 151165 ...
Page 39: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 6 4 151165 ...
Page 59: ...Cut Along the Dotted Line ...