Compatible Devices
151142
A-11
A.2
Two-Wire Smoke Detectors
Table A-2 lists two-wire smoke detectors that are compatible with the panel. The table is organized by
manufacturer. The columns show the number of detectors per loop that can be used.
The maximum number of smoke detectors per zone is determined by both the current draw and the
impedance of the smoke detector. If too many smoke detectors are used on any zone, false alarms
could occur.
Do not mix different models of detectors on any zone; false alarms could occur.
Do not mix detectors of different models unless the system is specifically intended to be installed in
that configuration.
Control unit Smoke Reset Time must be programmed for a number greater than or equal to the
maximum reset time of the smoke detector.
Table A-2 lists two-wire smoke detectors that are compatible with the 5895XL panel. The table is
Wheelock
(cont.)
ZRS-MCWH
x
Strobe
ZRS-24MCC
x
Strobe
ZRS-24MCCH
x
Strobe
MB-G6-24 x
Motor
Bell
MB-G10-24 x
Motor
Bell
MB-G6-12 x
Motor
Bell
MB-G10-12 x
Motor
Bell
MIZ-24-R x
Mini-Horn
MT-12/24-R x
x
Multitone Horn
MT4-12/2z
x
x
Multitone Horn
ZRS-MCW
x
Strobe
MTWPR-24MCCH
x
x
Multitone Horn Strobe
NH-12/24R
x
Horn
HSR
x
Horn/Strobe
HSW
x
Horn/Strobe
STR
x
Strobe
STW
x
Strobe
HNR
x
Horn
HNW
x
Horn
5895XL
Identifier
24H
Operating Voltage Range
18.5–27.4 VDC
Table A-1: Compatible Notification Appliances
Manufacturer
Model
Audio
Visual
Type