background image

 

July 2018 
443580499131 
 

Signify North America Corporation

 

200 Franklin Square Drive

 

Somerset, NJ  08873, USA

 

Phone:  855-486-2216

 

www.chloride-lighting.com

 

 

Signify Canada Ltd./Signify Canada Ltée. 
281 Hillmount Road,

 

Markham, ON, Canada  L6C 2S3

 

Phone:  800-668-9008

 

 

 

 

 

Fusion 

120 or 277VAC Input 

12VDC 72 Watt Output 

 

 
 
 
 
 
 
 
 
 

INSTALLATION AND 

OPERATING 

INSTRUCTIONS 

IMPORTANT 

SAFEGUARDS 

 
When  using  electrical  equipment,  basic  safety 
precautions should always be followed, including the 
following: 

 

READ AND FOLLOW ALL 

SAFETY INSTRUCTIONS 

 

All  servicing  should  be  performed  by  qualified 
personnel only. 
 
Equipment  should  be  mounted  in  locations  and  at 
heights  where  it  will  not  be  readily  subjected  to 
tampering by unauthorized personnel. 
 
The  use  of  accessory  equipment  not  recommended 
by the manufacturer may cause an unsafe condition. 
 
Do  not  use  this  equipment  for  other  than  intended 
use. 
 
Do not use outdoors. 
 
Do not let supply cords touch hot surfaces. 
 
Do not mount near gas or electric heaters. 
 
 
 

 
Caution:  Halogen  cycle  lamp(s)  are  used  in  this 
equipment.    To  avoid  shattering:    Do  not  operate 
lamp in excess of rated voltage, protect lamp against 
abrasion and scratches and against liquids when lamp 
is operating, dispose of lamp with care. 
 
Halogen  cycle  lamps  operate  at  high  temperatures.  
Do not store or place flammable materials near lamp. 
Use  caution  when  servicing  batteries.  Battery  acid 
can cause burns to skin and eyes. If acid is spilled on 
skin or eyes, flush acid with fresh water and contact 
a physician immediately. 
 
CAUTION:  To  avoid  electrical  overload,  total 
connected  lamp  load  (factory  and  field  installed) 
should not exceed output rating. 
 

SAVE THESE 

INSTRUCTIONS 

 

WARNING  –  Shut  off  AC  power  to  branch 
circuits  to  which  units  will  be  connected.  All 
wiring should be per N.E.C. Articles 501-4(b) and 
local codes. 
 
To  maintain  warranty,  equipment  with  batteries 
must  be  installed  or  placed  on  charge  within 
prescribed period after shipment. 

Summary of Contents for CHLORIDE Fusion F1WIC

Page 1: ...tended use Do not use outdoors Do not let supply cords touch hot surfaces Do not mount near gas or electric heaters Caution Halogen cycle lamp s are used in this equipment To avoid shattering Do not operate lamp in excess of rated voltage protect lamp against abrasion and scratches and against liquids when lamp is operating dispose of lamp with care Halogen cycle lamps operate at high temperatures...

Page 2: ...the outer surface of the stud before securing the backbox to the stud After sheetrock installation the leading edge of the backbox should be flush with the outer sheetrock surface room or finished surface Step 1 Sheetrock Ceiling Mount 14 1 4 x 9 1 8 cutout required Note This product is U L approved for use in IC rated ceiling constructions Remove one knockout in sheetmetal housing for AC service ...

Page 3: ...he four oblong knockouts in the short sides of the main housing and using the four 8 nuts provided Place bar hangers though the lowest set of holes in the adapters and attach to ceiling grid Adjust the vertical alignment so that the backbox flanges are flush with the bottom room side of the ceiling tile Step 2 Connect red battery lead by pushing connector halves together see above illustration Ref...

Page 4: ... Remove 4 pin lamp connector from main housing Push lamp sockets onto pins on MR 16 lamps Note The reflector lens system has been designed so that rotation of the system will not be required for most installations Reflectors and lenses may be rotated 90 if necessary Step 4 Connect flex cable connectors from circuit board assembly and cover together as shown The flex cable is keyed for proper align...

Page 5: ... this product operate at very high temperatures Care should be taken when servicing unit to avoid burns Note A This equipment is provided with a lockout feature whereby connecting battery leads prior to energizing AC power will not turn on the emergency lamps After AC power is energized the emergency lamps will turn on upon AC power failure B This equipment is provided with a low battery disconnec...

Page 6: ... diagnostic test Red LED indicator Single Flash battery fault Two Flashes lamp failure light bar failure EXIT signs Three Flashes charger fault Four Flashes transfer fault If more than one fault condition is present simultaneously the red LED will flash the indication pattern for each fault independently then repeat the cycle Pushbutton Test Switch Long Press longer than 0 5sec transfers product t...