Signet 8450-3 Pressure Transmitter

16

15

14

13

12

11

Signet 2450

Pressure Sensors

Terminals

White (Snsr 2 Gnd)

Red (Snsr 2 IN)

Black (Snsr 2 V+)

White (Snsr 1 Gnd)

Red (Snsr 1 IN)

Black (Snsr 1 V+)

3.1  Sensor Input Connections

-

 

+
-

+
-

-
+

-

+

 

+
-

-
+

 

-

-

+

+

-

6

5

4

3

2

1

6

5

4

3

2

1

6

5

4

3

2

1

6

5

4

3

2

1

6

5

4

3

2

1

*

Example:  Two transmitters connected to PLC/Recorder with separate power supply 

Loop 2 - 
 
Loop 2 + 
 
System Power Loop 1 - 
 
System Power Loop 1 + 
 
AUX Power - 
 
AUX Power + 

Loop 2 - 

 

Loop 2 + 

 

System Power Loop 1 - 

 

System Power Loop 1 + 

 

AUX Power - 

 

AUX Power + 

PLC or Recorder 

Channel 3 
4-20 mA in 

Channel 4 
4-20 mA in 

Transmitter 1 

Terminals 

Transmitter 2 

Terminals 

Channel 1 
4-20 mA in 

Channel 2 
4-20 mA in 

Power 

Supply 

12-24 VDC

 

 

* * 

*

Stand-alone application, no current loop used 

Transmitter 

Terminals 

Power 

Supply 

12-24 VDC

 

 

Connection to a PLC with built-in power supply 

Internal  

PLC Connection 

Connection to a PLC/Recorder, separate supply 

PLC or Recorder 

Loop 2 - 

 

Loop 2 + 

 

System Power Loop 1 - 

 

System Power Loop 1 + 

 

AUX Power - 

 

AUX Power + 

Transmitter 

Terminals 

Loop 2 - 

 

Loop 2 + 

 

System Power Loop 1 - 

 

System Power Loop 1 + 

 

AUX Power - 

 

AUX Power + 

Transmitter

Terminals

Loop 2 -

Loop 2 +

System Power Loop 1 -

System Power Loop 1 +

AUX Power -

AUX Power +

Power 

Supply 

12-24 VDC

 

 

PLC Terminals  

Channel 1 

4-20 mA 

Power 

Supply 

12-24 VDC 

Channel 2 

4-20 mA 

Channel 2 

4-20 mA 

Channel 1 

4-20 mA 

NC 
 
NC 

AUX power required only where two sensors are used

AUX power required only where two sensors are used 

AUX power required only where two sensors are used 

AUX power required only where two sensors are used

3.2  System Power/Loop Connections

Signet Pressure

Transmitter

Pressure Cal:

0.0    psi >

ENTER 

Signet Pressure

Transmitter

Pressure Cal:

0.0    psi >

ENTER

Transmitter

A + B 

”

 400 ft. (122 m)

J-box

Transmitter

 A + B + C 

”

 400 ft. (122 m)

Signet Pressure

Transmitter

Pressure Cal:

0.0    psi >

ENTER 

Transmitter 

”

 400 ft. (122 m)

Summary of Contents for 8450-3

Page 1: ...al panel cutout an adhesive template is provided as an installation guide Recommended clearance on all sides between instruments is 1 inch 2 Place gasket on instrument and install in panel 3 Slide mounting bracket over back of instrument until quick clips snap into latches on side of instrument 4 To remove secure instrument temporarily with tape from front or grip from rear of instrument DO NOT RE...

Page 2: ...es two sensors the total length of cable connected to the transmitter is limited to 400 ft The 3 conductors from a dual sensor system can be tied together and then a single set of wires continued on to the transmitter For best performance ground the sensor SHIELD wire to a local earth ground at a point near the sensor Experiment with connecting the sensor shield wire to different local ground poin...

Page 3: ...r supply Internal PLC Connection Connection to a PLC Recorder separate supply PLC or Recorder Loop 2 Loop 2 System Power Loop 1 System Power Loop 1 AUX Power AUX Power Transmitter Terminals Loop 2 Loop 2 System Power Loop 1 System Power Loop 1 AUX Power AUX Power Transmitter Terminals Loop 2 Loop 2 System Power Loop 1 System Power Loop 1 AUX Power AUX Power Power Supply 12 24 VDC PLC Terminals Cha...

Page 4: ... variable moves below the setpoint plus the hysteresis value Hysteresis Time Low Setpoint Process Output energized Output de energized Hysteresis Time High Setpoint Process VIEW menu During normal operation the ProcessPro displays the VIEW menu When using the CALIBRATE or OPTIONS menus the ProcessPro will return to the VIEW menu if no activity occurs for 10 minutes To select the item you want disp...

Page 5: ...diting Procedure Step 1 Press and hold ENTER key 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is UP UP UP DOWN keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW key to select menu item to be edited The first display element w...

Page 6: ... 20 mA output Pressure 1 Pressure 2 or Delta Pressure Pressure1 Pressure2 Loop 1 Range psi 0 0 100 0 Check the 2450 Sensor instructions for the range capability of your sensor Be sure to modify this setting if you change the Pressure Units Output 1 Source Pressure1 Select the INPUT SIGNAL represented by this Open Collector Output Pressure 1 Pressure 2 or the Delta Pressure Pressure1 Pressure2 Outp...

Page 7: ...le display and output response Select LOW HIGH or OFF Output1 Active Low Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active LOW This setting is used to turn a device OFF at the setpoint Output2 Active Low Loop1 Adjust 4 00 mA Adjust the minimum and maximum current output Use this setting to match the system output to any external device The display value represe...

Page 8: ...641 Heavy duty wall mount bracket 3 5000 598 198 840 225 Surface Mount Bracket 3 9000 392 159 000 368 Liquid tight connector kit for rear cover includes 3 connectors 3 9000 392 1 159 000 839 Liquid tight connector kit NPT 1 piece 3 9000 392 2 159 000 841 Liquid tight connector kit PG13 5 1 piece Display Condition Possible Causes Suggested Solutions Check Sensor Sensor not wired properly Sensor con...

Reviews: