background image

6

 2551 Magmeter 

8.1  Wiring: Frequency output (Compatible with all 

POWERED Signet Flow instruments.)

• 

When the blue jumper illustrated here is placed over both 
pins, the 2551-XX-11 outputs an open collector frequency 
signal that can be connected to any powered Signet 

fl

 ow 

meter. (Models 5075, 5500, 5600, 8550, 8900.)

• 

5 VDC power is provided to the 2551 Magmeter by all 
Signet 

fl

 ow instruments. No additional power is required.  

• 

If connecting the 2551 Magmeter to a 

fl

 ow instrument 

from another manufacturer, 5 to 24 VDC power must be 
provided to the 2551.  A 10 K

Ω

 pull up resistor must also 

be connected between terminals 1 and 2.

• 

The frequency output will be displayed as positive 

fl

 ow regardless of the 

fl

 ow direction.

8.2 Wiring: S

3

L output (Compatible with 8900 Multi-

Parameter Controller only)

• 

When the blue jumper illustrated here is removed (or 
placed over one pin for storage) the 2551-XX-11 outputs a 
digital (S

3

L) signal  compatible with the Signet 8900.

• 

The 2551 receives 5 VDC power from the 8900.  No 
additional power is required.

• 

The 8900 will display 0 (Zero) 

fl

 ow rate during periods 

of reverse 

fl

 ow.

• 

The maximum cable length from the 2551 to the 8900 
depends on the 8900 con

fi

 guration.  Refer to the 8900 

manual for complete information.

+5 VDC

S  L Data

3

Ground

Not used

1

2

3

4

3-8900.621C

I/O Module 3-8900.401-X

1

2

3

4

5

6

7

8

9

10

11

12

13

14

+5VDC (Black)

Freq. Input (Red)

GND (Shield)

+5VDC (Black)

Freq. Input 2 (Red)

S  L (Red)

GND (White/Shield)

+5VDC (Black)

S  L (Red)

GND (White/Shield)

3

3

Analog Output 1

Analog Output 2

(if applicable)

(if applicable)

Frequency

Input

1

Frequency

Input 2

OR

S3L

Input

2

S3L

Input

1

+

-

+

-

2551 Magmeter

Blue Jumper OFF = S

3

L OUT

S  L

3

3

4

8.  Wiring the 3-2551-11 with Frequency or Digital (S

3

L) output

1

2

3

4

5-24 VDC

Ground

Not used

Frequency Out

2551 Magmeter

10K

Ω

Install a pull-up resistor when connecting the
2551 Magmeter to other manufacturer's flowmeters.

2551 Frequency Out to other Manufacturer's equipment

Blue Jumper ON = FREQ OUT

3

4

Frequency

1

2

3

4

5-24 VDC

Ground

Not used

9

8

7

Sensr Gnd
(SHIELD)

Sensr IN
(RED)

Sensr V+
(BLACK)

2551 Magmeter

8550-1 Flow Transmitter

Frequency

AUX power MUST be connected on the 8550 to provide power 
to the 2551.

1

2

3

4

Ground

5-24 VDC

Not used

Frequency Out

2551 Magmeter

3-8900.621C

I/O Module 3-8900.401-X

1

2

3

4

5

6

7

8

+5VDC (Black)

Freq. Input (Red)

GND (Shield)

+5VDC (Black)

Freq. Input 2 (Red)

S  L (Red)

3

Frequency

Input

1

Frequency

Input 2

OR

S3L

Input

2

2551 Frequency Out to Signet 8900

2551 Frequency Out to Signet 8550-1

9.  Calibration and Software Con

fi

 guration

 

No calibration is necessary to begin using the 2551. 
The application and performance settings are pre-set to meet the requirements of most applications.

The 2551 application and performance settings can be customized using the 3-0250 USB to Digital (S

3

L) Con

fi

 guration / 

Diagnostic Tool and software. A Windows PC is required to adjust the following parameters:

• 

4 to 20 mA span

: Factory setting is 0 to 5 m/s.

 

Can be customized to any range.

• 

Noise Rejection Filter

: Factory set for 60 Hz.

 

Can be changed to 50 Hz.

• 

Low Flow Cutoff

: Factory setting is 0.05 m/s.

 

Can be customized to any velocity.

• 

Averaging Time

: Factory setting is 14 seconds

 

Can be customized from 0.1 seconds to 100 seconds

• 

Sensitivity

: Factory setting is 25% of full scale

 

Can be customized to any % of full scale

The

 MONITOR/VERIFY 

SENSOR 

function in the 

Signet 3-0250 Setup Tool 
software is very useful as a 
system troubleshooting tool.

MONITOR/VERIFY SENSOR

Summary of Contents for 2551

Page 1: ...two cable ports Use appropriate hardware to secure the 2551 from moisture intrusion One Liquid Tight Connector is included Sec 5 Pg 4 Topic Page 1 Quick Start Guide 1 2 Specifications 2 3 Installation Pipe Fittings 3 4 Selecting a Location 3 5 Hardware Configuration 4 6 General Installation and Grounding Tips 5 7 Wiring the Magmeter with 4 20 Loop 5 Topic Page 8 Wiring the Magmeter with Frequency ...

Page 2: ... PBT Display window Polyamide Electrical Power Requirements 4 to 20 mA 21 6 to 26 4 VDC 22 1 mA max Frequency 5 to 26 4 VDC 15 mA max Digital S3 L 5 to 6 5 VDC 15 mA max Reverse polarity and short circuit protected Current output 4 to 20 mA Loop Accuracy 32 μA max error 25 C 24 VDC Isolation Low voltage 48 VAC DC from electrodes and auxilary power Maximum cable 300 m 1000 ft Error condition 22 1 m...

Page 3: ...tance of straight pipe immediately upstream of the sensor Locating the sensor in a trap or where the flow is upward helps to protect the sensor from exposure to air bubbles when the system is in operation These configurations are not recommended because it is difficult to keep the pipe full Type Description 2 to 4 inch cut 1 7 16 inch hole in pipe Over 4 inch cut 2 1 8 inch hole in pipe 0 5 to 4 i...

Page 4: ...too deeply and damage the Magmeter wiring 1 2 3 4 JP2 White Yellow Red Black Brown Blue Not used The factory connects the sensor cable to the termin inside the yellow cover This blue jumper selects frequency output or S L serial data output in the 3 2551 XX 11 Not used on 4 20 mA models 3 The user must connect output cables to this 4 terminal block JP2 is for factory use only MAKE NO CONNECTIONS U...

Page 5: ...mps on metal pipes Fluid grounds must be in direct contact with the fluid and as near to the Magmeter as possible e The shield from the output cable must be terminated at the remote instrument ONLY This shield must not be connected at both ends f Connect an additional wire minimum AWG 14 2 08 mm2 from the remote instrument ground to the Magmeter ground terminal Grounding rings on plastic pipe Inst...

Page 6: ... Jumper OFF S3 L OUT S L 3 3 4 8 Wiring the 3 2551 11 with Frequency or Digital S3 L output 1 2 3 4 5 24 VDC Ground Not used Frequency Out 2551 Magmeter 10KΩ Install a pull up resistor when connecting the 2551 Magmeter to other manufacturer s flowmeters 2551 Frequency Out to other Manufacturer s equipment Blue Jumper ON FREQ OUT 3 4 Frequency 1 2 3 4 5 24 VDC Ground Not used 9 8 7 Sensr Gnd SHIELD...

Page 7: ...7 1 CPV8T015 325 56 86 01 92 15 348 78 SCH 80 PVC SADDLES FOR SCH 80 PVC PIPE 2 PV8S020 193 83 51 21 154 77 585 81 2 PV8S025 138 01 36 46 217 38 822 78 3 PV8S030 83 89 22 16 357 62 1353 60 4 PV8S040 40 88 10 80 733 88 2777 74 6 PV8S060 22 53 5 95 1331 85 5041 06 8 PV8S080 12 52 3 31 2395 41 9066 64 10 PV8S100 7 94 2 10 3778 75 14302 57 12 PV8S120 5 71 1 51 5256 69 19896 57 SCH 80 PVC SADDLES FOR S...

Page 8: ...8 34 DN20 SFMT007 1158 05 305 96 25 91 98 05 DN25 SFMT010 749 09 197 91 40 05 151 58 DN32 SFMT012 439 51 116 12 68 26 258 36 DN40 SFMT015 248 93 65 77 120 52 456 16 DN50 SFMT020 146 85 38 80 204 30 773 26 PVC FITTINGS DIN ISO BS ANSI DN15 PVMT005 2067 76 546 30 14 51 54 91 DN20 PVMT007 1136 61 300 29 26 39 99 90 DN25 PVMT010 716 52 189 31 41 87 158 47 DN32 PVMT012 446 07 117 85 67 25 254 56 DN40 P...

Page 9: ...5 4 CR4W040 36 84 9 73 814 34 3082 28 5 CR4W050 29 28 7 73 1024 70 3878 50 6 CR4W060 20 29 5 36 1478 26 5595 21 8 CR4W080 11 73 3 10 2557 72 9680 96 10 CR4W100 7 45 1 97 4028 83 15249 13 12 CR4W120 5 24 1 39 5722 73 21660 53 CARBON STEEL WELDOLETS ON SCH 40 PIPE 2 CS4W025 105 70 27 93 283 82 1074 27 3 CS4W030 70 68 18 67 424 45 1606 56 4 CS4W040 36 38 9 61 824 65 3121 30 5 CS4W050 29 28 7 73 1024 ...

Page 10: ...K Factor K Factor 20 mA 20 mA IN TYPE Gallons Liters in GPM in LPM BRONZE TEES ON SCH 40 PIPE 1 BR4T010 582 34 153 86 51 52 194 99 1 BR4T012 330 54 87 33 90 76 343 53 1 BR4T015 254 76 67 31 117 76 445 71 2 BR4T020 157 36 41 58 190 64 721 58 COPPER TEES FITTING ON COPPER PIPE SCH K CUKT005 2459 19 649 72 12 20 46 17 CUKT007 1108 02 292 74 27 08 102 48 1 CUKT010 649 87 171 70 46 16 174 73 1 CUKT012 ...

Page 11: ...follow local ordinances when disposing of this or any product with electronic components Soak sensor overnight in fluid Modify grounding to protect the Magmeter from interference Set low flow cutoff higher Return to factory for service Use 3 0250 Setup tool to respan the Magmeter to match Loop device Respan Loop device to match Magmeter Set Range Jumper correctly Return to factory for service 2551...

Page 12: ... output 3 2551 P 0 1 2 Example Part Number Replacement parts and Accessories Mfr Part No Code Description 1220 0021 198 801 186 O ring FPM 1224 0021 198 820 006 O ring EPDM 1228 0021 198 820 007 O ring FFPM 3 2551 11 159 001 215 Magmeter electronics no display frequency or digital S3 L output 3 2551 12 159 001 216 Magmeter electronics no display 4 to 20 mA output 3 2551 P0 159 001 211 PP 316L SS D...

Reviews: