The PDU comes either in 19 inches version (horizontal
placement) or 0U version (vertical placement). This information
is usually pre-defined at the ordering procedure.
Note: Please refer to the respective user manual of the PDU
for any more detailed information on how to use or setup the
PDU.
4
Maintenance
One of the biggest advantages of the MicroDC is the very low
maintenance cost needed in order the system to operate and
function as brand new.
4.1
Cooling device
Caution! Before embarking on any maintenance work,
switch current off of the cooling unit.
The cooling unit is a low maintenance type; so no filter change
is required. The main job that regularly needed to be done is
to blow the internal components with compressed dry air at
a maximum pressure of 4 bars; the following also shall be
checked regularly:
Job
Frequency
Check the external air to air heat exchanger
and clean if necessary
Every 3 months
Check effectiveness of the condensate dis-
charge hose to check whether it has been
blocked or not
Every 3 months
Check the fans for any overheating signs or
paranormal vibration
Every 6 months
www.signamax.com
Micro Data Center Technical Manual 17