10
SignalFire Telemetry
Rev 1.6
Mounting and Care
The unit comes with a watertight ½” NPT conduit fitting on the bottom mounting plate. The
Sentinel is then directly mounted to the sensor with a short section of conduit.
Direct Mount to Sensor with Short Conduit
This mounting method uses a short conduit run from the sensor and the unit is held in place by the conduit.
WARNING: The Sentinel must be mounted in a location free of high vibrations. Over time
vibrations can damage the Sentinel or battery pack, which could impair its safety ratings.
Do not mount directly to continuous vibrating equipment such as pumps or compressors.