SignalFire Telemetry
28
42034
2033
Radio packets per minute alert. 0 if packets/min <= 60, 1 if packets/min >
60
42035
2034
State of Digital Output 1. 0=open, 1=closed (readable with function code
0x01 or 0x03, writeable with function code 0x05, 0x06, 0x16)
42036
2035
State of Digital Output 2. 0=open, 1=closed (readable with function code
0x01 or 0x03, writeable with function code 0x05, 0x06, 0x16)
42037
2036
State of Digital Input 1. 0=open, 1=closed (readable with function code 0x02
or 0x03)
42038
2037
State of Digital Input 2. 0=open, 1=closed (readable with function code 0x02
or 0x03)
42039
2038
Analog Input 1 (mV)
42040
2039
Analog Input 2 (mV)
42041
2040
Analog Input 3 (mV)
42101
2100
Address test register. Always returns 2100
42102
2101
Address test register. Always returns 2101
42103
2102
Address test register. Always returns 2102
43001
3000
Write the radio address of a Modbus Stick node to this register to cause that
Modbus Stick to perform a scan for attached Modbus sensors
43004
3003
Write Modbus ID for a Modbus Client node to this register to cause that
remote node to perform a scan for attached Modbus sensors
44002
4001
Status of Slave ID 1:Returns 1 if Slave is present and 0 if not present
44003
4002
Status of Slave ID 2:Returns 1 if Slave is present and 0 if not present
…
…
…
44241
4240
Status of Slave ID 240:Returns 1 if Slave is present and 0 if not present
47001
7000
Event 1
–
RSD Line Number
47002
7001
Event 1
–
Source SID
47003
7002
Event 1
–
Destination RSD SID
47004
7003
Event 1
–
Destination RSD relay channel
47005
7004
Event 1
–
RSD Event Type: 1 = Energize, 0 = De-Energize
47006
7005
Event 2
–
RSD Line Number
…
…
…
47011
7010
Event 3
–
RSD Line Number
…
…
…
47016
7015
Event 4
–
RSD Line Number
…
…
…
47021
7020
Event 5
–
RSD Line Number
…
…
…
47025
7024
Event 5
–
RSD Event Type: 1 = Energize, 0 = De-Energize