S-DIAS SAFETY DIGITAL INPUT MODULE
SDI 101
02.12.2019
Page 13
3
Technical Data
3.1
Input Specifications
The inputs are Type 1 in accordance with EN 61131-2
Number
10
Input voltage
+24 V DC
Input voltage range
m18 V
m30 V
Signal level
low: ≤ +5 V
high: ≥ +15 V
Switching threshold
typ11 V
Input current
3 mA at +24 V
Input delay
0.5 ms
3.2
Signal Output Specifications for Cross-Circuit Detection
Number
5x signal A
5x signal B
Rated output voltage
+24 V DC
Output voltage range
m18 V
m30 V
Output current
100 mA at +24 V
Miscellaneous
short-circuit proof
The clock outputs A and B are generated once internally and are wired in parallel to
the connectors. A direct cross-circuit of Clock A and/or B of a connector therefore
results in cross-circuit detection in all channels.
When using the digital inputs with the clock outputs for cross-fault detection for long
cable lengths, make sure that the cable capacitance from the clock output to the
digital input does not exceed a value of 100 nF and that the cable resistance does not
exceed a value of 250 Ω, so that the cross-fault detection does not detect a wiring
error with proper wiring.