S-DIAS SAFETY CPU MODULE
SCP 111-S
19.10.2021
Page 13
3.2
Electrical Requirements
3.2.1
Module Supply (Input)
Supply voltage
+18-30 V DC, typ24 V DC
SELV/PELV
1)
Current, internal consumption
typically 90 mA internal consumption
maximum 1.5 A
2), 3)
Current consumption
from the S-DIAS bus
+5 V
+24 V
with missing
+24 V connection (X3)
typically
250 mA
maximum
300 mA
0 A
0 A
with existing
+24 V connection (X3)
0 A
0 A
0 A
0 A
A fuse for the supply voltage must be installed, which can sufficiently limit voltage
and current.
Un fusible conforme aux limites de la tension et du courant d'alimentation doit être
présent en amont de l'alimentation.
1)
For USA and Canada:
The supply must be limited to:
a) max. 5 A at voltages from 0-20 V DC, or
b) 100 W at voltages from 20-60 V DC
The limiting component (e.g. transformer, power supply or fuse) must be certified by an NRTL
(Nationally Recognized Testing Laboratory).
1)
Pour les États-Unis et le Canada:
L’alimentation doit être limitée à:
a) max. 5 A pour des tensions de 0-20 V DC, ou
b) 100 W pour des tensions de 20-60 V DC
Le composant imposant la limite (par exemple, transformateur, alimentation électrique ou
fusible) doit être certifié par un NRTL (National Recognized Testing Laboratory, par exemple,
UL).