C-DIAS SAFETY DIGITAL INPUT MODULE
CSDI 162
1.3
Page 11
Technical Data
Input specifications
The inputs are type 1 according to IEC/EN 61131
Number of …
16
Input voltage
+24 V DC
Input voltage range
M18 V
M30 V
Signal level
Low: ≤ +5 V
High: ≥ +15 V
Switching threshold
Typ11 V
Input current
5 mA at +24 V
Input delay
Maximum 2.5 ms
Table 2: Input specifications
Specifications for the cross-circuit detection signal outputs
Number of …
2
Rated output voltage
+24 V DC
Output voltage range
M18 V
M30 V
Output current
100 mA at +24 V
Miscellaneous
Short-circuit proof
Table 3: Clock output specifications
When using the digital inputs with the clock outputs for cross-wire detection for long
cable lengths, it must be ensured that the cable capacitance from the clock output to
the digital input does not exceed a value of 75 nF in relation to GND and that the
cable resistance does not exceed a value of 250 Ω, so that the cross-wire detection
does not detect a wiring fault if the wiring is correct.