![SIGMATEK AI 022-1 Operating Manual Download Page 22](http://html1.mh-extra.com/html/sigmatek/ai-022-1/ai-022-1_operating-manual_1268131022.webp)
AI 022-1
S-DIAS STRAIN GAUGE INPUT MODULE
Page 20
04.11.2020
7.2
Analog Inputs
ADC configura-
tion valid
State
1
The configuration of the ADCs is valid => the analog values can
be used in the application
0
The configuration of the ADCs is invalid
-1
Error while sending the configuration to the ADCs
Analog Input [1-
4]
Input
Current value of the respective analog channel (if AI1[1-2]ConfigValid, as well
as the Ready bit of the AI[1-2]ADCState is set) Displays the value
16#80000010 if the ErrorBit on the server AI[1-2]ADCState is set.
Zero Scale Off-
set for AI [1-2]
Output
Scale null point according to the last calibration (updated with each change in
the FilterDepth, SincSetting, Gain or OpMode settings)
Full Scale Off-
set for AI [1-2]
Output
Scale end value according to the last calibration (updated with each change
in the FilterDepth, SincSetting, Gain or OpMode settings)
AI[1-
2]ADCState
State
Shows the status of the respective input:
Bit 0-4
Not used
Bit 5
No reference (set if the reference voltage is too low)
Bit 6
error
The ADC error bit is set when all bits in the analog value were
referenced to 0 or 1. The bit is cleared when
the
error
no
longer
exists
and
the
analog
value
valid
again.
Possible Causes:
-Value outside of the valid measurement range
- No reference voltage
Bit 7
Not Ready
Indicates when newly converted values are available (for valid
values, it is always set to 0 in Continuous mode)
AI[1-2]Fil-
terDepth
Property
Value setting for the filter depth of the respective ADC
(as a default 2)
Valid range of values: 2-1023
AI[1-2]SincSet-
ting
Property
Selection of the sinc filter type of the respective ADC:
0
sinc 4 Filter is used (default)
1
sinc 3 Filter is used (default)
The advantage of the sinc 3 filter, as compared with sinc 4 filter, is the lower
settling time. The sinc 4 filter however, provides better 50 / 60 Hz suppression.
AI[1-2] Gain
Property
Gain selection to select the input range of the respective ADC:
0
Gain 1 (± 80 mV)
1
Not used (if selected, the default value is used)
2
Not used (if selected, the default value is used)
3
Gain 8 (± 10 mV) (default)
4
Gain 16 (± 5 mV)
5
Gain 32 (± 2,5 mV)
6
Gain 64 (± 1,25 mV)
Operating mode
for AI[1-2]
Output
Selection of operating mode for the respective ADC:
0
Continuous conversion mode (default)
6
System zero-scale calibration
7
System full-scale calibration
Reset to Fac-
tory Settings
Output
-1
Function not available (available starting with FW version 1.80)
Summary of Contents for AI 022-1
Page 8: ...AI 022 1 S DIAS STRAIN GAUGE INPUT MODULE Page 6 04 11 2020...
Page 10: ...AI 022 1 S DIAS STRAIN GAUGE INPUT MODULE Page 8 04 11 2020 2 Mechanical Dimensions...
Page 11: ...S DIAS STRAIN GAUGE INPUT MODULE AI 022 1 04 11 2020 Page 9 3 Connector Layout...
Page 14: ...AI 022 1 S DIAS STRAIN GAUGE INPUT MODULE Page 12 04 11 2020 4 Wiring 4 1 Wiring Example...