Sigmatek FDD Sizes 7 to 9 Power Installation Guide
53
S
P
M
El
Te
UL
list
ing
in
Table 4-4 Size 7 to 9 Model and Line reactor part number
(For purchase contact
SIGMATEK)
Figure 4-4 Input line reactor dimensions
Table 4-5 Input line reactor ratings (2 %)
4.2.3
Input inductor calculation
To calculate the inductance required (at
Y
%), use the following equation:
Where:
I
= drive rated input current (A)
L
= inductance (H)
f
= supply frequency (Hz)
V
= voltage between lines
Size
Drive model
Inductor model
Line reactor part
number
7
074.00660
INL 4014
4401-0237
074.00770
INL 4015
4401-0238
074.01000
INL 4016
4401-0239
8
084.01340
INL 4017
4401-0240
084.01570
INL 4018
4401-0241
9
094.02000, 094.02240
INL 401
4401-0181
Part
number
Model
Current Inductance
Overall
width
(W)
Overall
depth
(D)
Overall
height
(H)
Weight
Max
ambient
temp
Min
airflow
Maximum
losses
Quantity
required
A
H
mm
mm
mm
kg
°C
m/s
W
4401-0237 INL 4014
74
200
254
130
195
12
50
0
129
1
4401-0238 INL 4015
88
170
254
150
195
14
50
0
127
1
4401-0239 INL 4016
105
140
254
150
195
14
50
0
139
1
4401-0240 INL 4017
155
95
290
160
205
20
50
0
182
1
4401-0241 INL 4018
177
83
290
170
205
22
50
0
200
1
4401-0181
INL 401
245
63
240
190
225
32
50
1
148
1
4401-0182
INL 402
370
44
276
200
225
36
50
1
205
1
4401-0184
INL 602
202
133
276
200
225
36
50
1
116
1
H
W
D
L
Y
100
----------
V
3
-------
1
2
f
I
------------
=
Summary of Contents for 074.00660
Page 1: ...Power Installation Guide SIGMATEK FDD Frame 7 to 9 Issue 12...