Sigmatek FDD Sizes 7 to 9 Power Installation Guide
2.4
Ratings
Table 2-1 400 V drive ratings, cable sizes and fuse ratings
* These fuses are fast acting.
** These ratings are for 2 kHz switching frequency. For ratings at 3 kHz switching frequency refer to the Power and
current ratings in section 5.1.2
Power and current ratings (Derating for switching frequency and
Table 2-2 Protective ground cable ratings
Fuses
The AC supply to the drive must be installed with suitable protection against overload and
short-circuits. The following section shows recommended fuse ratings. Failure to observe
this requirement will cause risk of fire.
Nominal cables sizes below are based on the cable installation method B2 (ref: IEC60364-
5-52:2001) unless otherwise specified, and are provided as a guide only. Ensure cables
used suit local wiring regulations.
Model
Max.
cont.
input
current
Fuse
Nominal cable size
Normal Duty
Heavy Duty
European
USA
IEC
UL
Input Output Input Output
Max.
cont.
output
current
Nom
power
@
400 V
Motor
power
@
460 V
Max.
cont.
output
current
Nom
power
@
400 V
Motor
power
@
460 V
3ph
Nom
Class
Nom
Class
A
A
A
mm
2
mm
2
AWG
or
kcmil
AWG
or
kcmil
A
kW
hp
A
kW
hp
074.00660
74
100
gG
80
CC,
J or
T*
35
35
1
1
79
37
60
66
30
50
074.00770
88
100
100
50
50
2
2
94
45
60
77
37
60
074.01000
105
125
125
70
70
1/0
1/0
112
55
75
100
45
75
084.01340
155
250
gR
225
HSJ
2 x 50 2 x 50
2 x 1
2 x 1
155
75
100
134
55
100
084.01570
177
250
225
2 x 70 2 x 70 2 x 1/0 2 x 1/0
184
90
150
157
75
125
094.02000
232
315
gR
300
HSJ
2 x 70
(B1)
2 x 95
(B2)
2 x 3/0 2 x 2/0
221
110
150
200**
90
150
094.02240
267
350
2 x 95
(B1)
2 x 120
(B2)
2 x 4/0 2 x 4/0 266**
132
200
224**
110
150
on page 79 for maximum fuse rating, maximum
cable size and peak currents.
Input phase conductor size
Minimum ground conductor size
≤
10 mm
2
Either 10 mm
2
or two conductors of the same cross-sectional area as the input
phase conductor
> 10 mm
2
and
≤
16 mm
2
The same cross-sectional area as the input phase conductor
> 16 mm
2
and
≤
35 mm
2
16 mm
2
> 35 mm
2
Half of the cross-sectional area of the input phase conductor