background image

3

SOURCE:

There are 32 illuminated source buttons on the panel. The LED incorporated into

each source button tracks the LEVEL 1 selection. The LED’s only illuminate when the input is
within the range of the panel. For example, if the panel is set for sources 1-32, but the Level 1
window is displaying 108, no LED will be on. This may occur if the switch was performed by a
different control panel or via the serial port.

The group select DIP switch on the rear of the control panel determines to which group of 32

sources this panel is assigned. This panel can control sources 1-32, 33-64, 65-96 or 97-128. Refer
to the chart in the next section to select the desired source group assignment.

The SBX-32 will only function with valid source data received from the SCI-ADX system

control interface module. If SCI-ADX is set for 16 sources, the only SOURCE switches that are
functional are 1-16. Another example would be if the SCI-ADX is set for 48 sources and the SBX
panel was set to the SOURCE group 33-64, only switches 33-48 would be operational on the
panel.

TAKE:

 The red switch on the right side of the control panel is the TAKE button. When pressed, it

sends the SCI-ADX a request to change the OUTPUT to the preset condition. The status of the
switch request will be transmitted back to the panel by the SCI-ADX. When the control panel
receives the updated status, the display will stop flashing and reflect the current status of that
output. It should be noted that although there may be a slight delay before the display stops
flashing after pressing the TAKE button, the actual switch is made immediately by the SCI. The
control panel update is slightly delayed as it awaits the response from the SCI-ADX. If the displays
remain flashing after a TAKE is generated, there is possibly a problem with the SCI or the COMM
line.

The selected OUTPUT of the control panel can be reviewed by pressing the TAKE key. The

OUTPUT will be displayed in the LEVEL 4 window for 2 seconds. This must be done when there
are no preset conditions.

AUTOTAKE: 

The panel is also capable of switching without the use of the TAKE switch. This

is accomplished by setting DIP switch S1,7 to ON, at the rear of the control panel.  Reminder:
power to the control panel must be  reset whenever the DIP switch configuration is changed. In the
AUTOTAKE mode, the transaction is performed at the completion of the source selection.

OUTPUT: 

The panel is capable of addressing any output from 1 to 128. The charts in the

following section will show how to set the switches for the desired output.

ERROR MESSAGES:

There are two possible errors that can occur if the rear panel DIP

switches are not set to a valid configuration.

If the panel is set up for an 

OUTPUT

 address that exceeds the maximum output value on the

SCI-ADX, the illuminated keys will scan rapidly from the right to the left.

If the panel is set up for a 

SOURCE

 group that exceeds the maximum input value on the SCI-

ADX, the illuminated keys will scan rapidly from the left to the right. For example, if the panel is set
for Inputs 97-128, but the SCI-ADX is set for Inputs 1-64 or less.

In either case the problem must be corrected at the control panel or the SCI-ADX. Typically

this problem will be due to the control panel being improperly configured. The control panel must
be turned off and on again before proper operation will begin.

In addition to these error indicators, there is one other potential problem in which the SBX will

raise a flag. If for any reason the SBX is unable to communicate with the SCI-ADX, which is the
control interface card located in the master frame, the requested input will flash. This is an
indication that there is a communication problem in the system. The most likely cause would be a
faulty or disconnected coaxial COMM cable.

Summary of Contents for SBX-32

Page 1: ...SBX 32 SINGLE BUS CONTROL PANEL OPERATOR S MANUAL SIGMA ELECTRONICS INC 1027 COMMERCIAL AVENUE EAST PETERSBURG PA 17520 717 569 2681 P O Box 448 ...

Page 2: ...ol panel are four LEVEL buttons This allows selection of any one of the four levels When no LEVEL button has been selected the panel is operating in a FOLLOW mode A single momentary press of the desired level button activates a LEVEL that causes the respective display to go blank This operation will allow a BREAKAWAY where only one level is changed or a SPLIT where multiple levels select different...

Page 3: ...em with the SCI or the COMM line The selected OUTPUT of the control panel can be reviewed by pressing the TAKE key The OUTPUT will be displayed in the LEVEL 4 window for 2 seconds This must be done when there are no preset conditions AUTOTAKE The panel is also capable of switching without the use of the TAKE switch This is accomplished by setting DIP switch S1 7 to ON at the rear of the control pa...

Page 4: ...2 S1 3 S1 4 S1 5 S1 6 1 OFF OFF OFF OFF OFF ON 2 OFF OFF OFF OFF ON OFF 3 OFF OFF OFF OFF ON ON 4 OFF OFF OFF ON OFF OFF 5 OFF OFF OFF ON OFF ON 6 OFF OFF OFF ON ON OFF 7 OFF OFF OFF ON ON ON 8 OFF OFF ON OFF OFF OFF 9 OFF OFF ON OFF OFF ON 10 OFF OFF ON OFF ON OFF 11 OFF OFF ON OFF ON ON 12 OFF OFF ON ON OFF OFF 13 OFF OFF ON ON OFF ON 14 OFF OFF ON ON ON OFF 15 OFF OFF ON ON ON ON 16 OFF ON OFF ...

Page 5: ...ON 42 ON OFF ON OFF ON OFF 43 ON OFF ON OFF ON ON 44 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON 46 ON OFF ON ON ON OFF 47 ON OFF ON ON ON ON 48 ON ON OFF OFF OFF OFF 49 ON ON OFF OFF OFF ON 50 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON 52 ON ON OFF ON OFF OFF 53 ON ON OFF ON OFF ON 54 ON ON OFF ON ON OFF 55 ON ON OFF ON ON ON 56 ON ON ON OFF OFF OFF 57 ON ON ON OFF OFF ON 58 ON ON ON OFF ON OFF ...

Page 6: ... is to be controlled SOURCE GROUP S2 1 S2 2 1 32 OFF OFF 32 64 OFF ON 65 96 ON OFF 97 128 ON ON SBX 32 OUTPUT ADDRESS OUTPUT S2 3 S2 4 S2 5 S2 6 S2 7 S2 8 S2 9 1 OFF OFF OFF OFF OFF OFF ON 2 OFF OFF OFF OFF OFF ON OFF 3 OFF OFF OFF OFF OFF ON ON 4 OFF OFF OFF OFF ON OFF OFF 5 OFF OFF OFF OFF ON OFF ON 6 OFF OFF OFF OFF ON ON OFF 7 OFF OFF OFF OFF ON ON ON 8 OFF OFF OFF ON OFF OFF OFF 9 OFF OFF OFF...

Page 7: ...FF ON ON OFF ON 46 OFF ON OFF ON ON ON OFF 47 OFF ON OFF ON ON ON ON 48 OFF ON ON OFF OFF OFF OFF 49 OFF ON ON OFF OFF OFF ON 50 OFF ON ON OFF OFF ON OFF 51 OFF ON ON OFF OFF ON ON 52 OFF ON ON OFF ON OFF OFF 53 OFF ON ON OFF ON OFF ON 54 OFF ON ON OFF ON ON OFF 55 OFF ON ON OFF ON ON ON 56 OFF ON ON ON OFF OFF OFF 57 OFF ON ON ON OFF OFF ON 58 OFF ON ON ON OFF ON OFF 59 OFF ON ON ON OFF ON ON 60 ...

Page 8: ... ON ON 100 ON ON OFF OFF ON OFF OFF 101 ON ON OFF OFF ON OFF ON 102 ON ON OFF OFF ON ON OFF 103 ON ON OFF OFF ON ON ON 104 ON ON OFF ON OFF OFF OFF 105 ON ON OFF ON OFF OFF ON 106 ON ON OFF ON OFF ON OFF 107 ON ON OFF ON OFF ON ON 108 ON ON OFF ON ON OFF OFF 109 ON ON OFF ON ON OFF ON 110 ON ON OFF ON ON ON OFF 111 ON ON OFF ON ON ON ON 112 ON ON ON OFF OFF OFF OFF 113 ON ON ON OFF OFF OFF ON 114 ...

Page 9: ...s for the COMM input signal comparator The direction of the COMM line is controlled by P3 7 and is normally in the receive mode except when a panel transaction is made U2 provides the reset function to the microprocessor upon three different conditions The first is a power on reset The second is at any time the 5 VDC power supply goes below 4 5 VDC a brownout condition Third is when the microproce...

Reviews: