Technical Data
47
Relay non-energized
Bump test
IEC60255-21-2
Class 1
10 g, 16 ms duration
1000 shocks in both directions of 3
axes
Relay non-energized
Seismic test
IEC60255-21-3
Class 1
X-axis 1 Hz to 8/9 Hz: 7.5 mm
X-axis 8/9 Hz to 35 Hz :2 g
Y-axis 1 Hz to 8/9 Hz: 3.75 mm
Y-axis 8/9 Hz to 35 Hz :1 g
1 sweep cycle in each axis,
Relay energized
Climatic tests
Item
Standard
Data
Cold test - Operation
IEC60255-27
IEC60068-2-1
-10°C, 16 hours, rated load
Cold test
– Storage
IEC60255-27 IEC60068-2-1
-25°C, 16 hours
Dry heat test
– Operation
[IEC60255-27
IEC60068-2-2
+55°C, 16 hours, rated load
Dry heat test
– Storage
IEC60255-27
IEC60068-2-2
+70°C, 16 hours
Change of temperature
IEC60255-27
IEC60068-2-14
Test Nb, figure 2, 5 cycles
-10°C / +55°C
Damp heat static test
IEC60255-27
IEC60068-2-78
+40°C, 93% r.h. 10 days, rated load
Damp heat cyclic test
IEC60255-27
IEC60068-2-30
+55°C, 93% r.h. 6 cycles, rated load
CE Certificate
Item
Data
EMC Directive
EN 61000-6-2 and EN61000-6-4 (EMC Council
Directive 2004/108/EC)
Low voltage directive
EN 60255-27 (Low-voltage directive 2006/95 EC).