Technical data
39
Inrush Current
IEC60255-1
T ≤ 10 ms/I≤ 25 A per power supply
module,
Binary inputs
Item
Standard
Data
Input voltage range
IEC60255-1
110/125 V DC
220/250 V DC
Threshold1: guarantee
operation
IEC60255-1
154V, for 220/250V DC
77V, for 110V/125V DC
Threshold2: uncertain operation
IEC60255-1
132V, for 220/250V DC;
66V, for 110V/125V DC
Response time/reset time
IEC60255-1
Software provides de-bounce
time
Power consumption, energized
IEC60255-1
Max. 0.5 W/input, 110V DC
Max. 1 W/input, 220V DC
Binary outputs
Item
Standard
Data
Max. system voltage
IEC60255-1
250V DC/AC
Current carrying capacity
IEC60255-1
5 A continuous,
30A
,
200ms ON, 15s OFF
Making capacity
IEC60255-1
1100 W(DC) at inductive load with
L/R>40 ms
1000 VA(AC)
Breaking capacity
IEC60255-1
220VDC
, 0.15A, at L/R≤40 ms
110VDC
, 0.30A, at L/R≤40 ms
Mechanical endurance, Unloaded
IEC60255-1
50,000,000 cycles (3 Hz switching
frequency)
Mechanical endurance, making
IEC60255-1
≥1000 cycles
Mechanical endurance, breaking
IEC60255-1
≥1000 cycles
Specification state verification
IEC60255-1
IEC60255-23
IEC61810-1
UL/CSA
、
TŰV