1-18

Attach insulation sleeve

Round crimp-style terminal

Electric wire

Connect wires of the 
same gauge to both side.

Do not connect wires of the 
same gauge to one side.

Do not connect wires 
of different gauges.

All wires must be 

Þ

 rmly connected.

Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts.
The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
Make sure no external pressure is applied to the terminal connectors and wires.
Make sure all the covers are properly 

Þ

 xed to avoid any gap.

Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching 
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).







Use the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
Over tightening can damage the terminal screw.
Do not connect wire of different gauge to same terminal.
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.




R410A is a new HFC refrigerant which does not damage the 
ozone layer. The working pressure of this new refrigerant is 1.6 
times higher than conventional refrigerant (R22), thus proper 
installation / servicing is essential.

Never use refrigerant other than R410A in an air conditioner 
which designed to operate with R410A.
POE or PVE oil is used as lubricant for R410A compressor, 
which  is  different  from  the  mineral  oil  used  for  R22 
compressor. During installation or servicing, extra precaution 
must be taken not to expose the R410A system too long 
to moist air. Residual POE or PVE oil in the piping and 
components can absorb moisture from the air.
To prevent mischarging, the diameter of the service port on 
the 

ß

 are valve is different from that of R22.

Use tools and materials exclusively for refrigerant R410A. 
Tools exclusively for R410A are manifold valve, charging 
hose, pressure gauge, gas leak detector, 

ß

 are tools, torque 

wrench, vacuum pump and refrigerant cylinder.
As an R410A air conditioner incurs higher pressure than 
R22 units, it is essential to choose the copper pipes correctly. 
Never use copper pipes thinner than 0.8mm even though 
they are available in the market. 
If the refrigerant gas leakage occurs during installation / 
servicing, be sure to ventilate fully. If the refrigerant gas 
comes into contact with 

Þ

 re, a poisonous gas may occur.

When installing or removing an air conditioner, do not allow 
air or moisture to remain in the refrigerant cycle.

SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT

Vacuuming is necessary to eliminate all moisture and air from the system.

Vacuuming The Piping And The Indoor Unit

The  indoor  unit  and  the  refrigerant  connection  pipes  must 
be  air-purged  because  the  air  containing  moisture  that 
remains  in  the  refrigerant  cycle  may  cause  malfunction  of 
the compressor.

Remove the caps from the valve and the service port.
 Connect the center of the charging gauge to the vacuum 
pump.
 Connect the charging gauge to the service port of the 3-
way valve.


VACUUMING AND CHARGING

 Start  the  vacuum  pump.  Evacuate  for  approximately 
30  minutes.  The  evacuation  time  varies  with  different 
vacuum pump capacity. Con

Þ

 rm that the charging gauge 

needle has moved towards -760mmHg.

Caution

 If the gauge needle does not move to -760mmHg, be sure to 
check for gas leaks (using the refrigerant detector) at 

ß

 are 

type connection of the indoor and outdoor unit and repair 
the leak before proceeding to the next step.
 Close the valve of the changing gauge and stop the vacuum 
pump.

Summary of Contents for AHQ100AV1

Page 1: ...Installationshandbuch Split Typ Einheit Installatiehandleiding Werdelen Drukletter Eenheid Manual De Instalación Escisión tipos Unidades Руководство по установке Блок Раздельного Типа Kurulum kılavuzu Ayrılma Tipi Üniteleri Εγχειρίδιο Εγκατάστασης Διαίρεση Τύπος Μονάδα Manual De Instalação Split Tipo Unidades English Français Deutsch Nederlands Español Русский Türkçe Ελληνικά Português ...

Page 2: ......

Page 3: ...ll dimensions are in mm G B D E C F A Dimension Model A B C D E F G AHQ71AV1 1080 65 630 400 230 218 928 Indoor Unit AHQ100 125AV1 All dimensions are in mm A B E C D F G Dimension Model A B C D E F G AHQ100AV1 1490 1308 74 1538 268 635 259 AHQ125AV1 1738 1556 74 1786 268 635 259 ...

Page 4: ...1 2 Indoor Unit AHQ140AV1 All dimensions are in mm Dimension Model A B C D E F G H I J K L AHQ140AV1 1750 40 36 1903 1830 680 352 292 285 140 1880 250 D B C C C C B A J I G F H L E C K ...

Page 5: ...il vapour or oil steam exist this may cause plastic part to melt or deform as a result of excessive heat or chemical reaction When the unit is used in kitchen keep ßouraway from going into suction of the unit This unit is not suitable for factory used where cutting oil mist or iron powder exist or voltage ßuctuates greatly Do not install the units at area like hot spring or oil reÞnery plant where...

Page 6: ...ion is convenient for wiring and piping Standard Mounting Ensure that the overhead supports are strong enough to hold the weight of the unit Position the hanger rods wall mounting bracket for ßoor standing and check for its alignment with the unit as shown in Figure A Also check that the hangers are secured and the base of the fan coil unit is leveled in both horizontal directions taking into acco...

Page 7: ...discharge air with the warm return air Do not install the indoor unit where there is direct sunlight shining on the unit The location should be suitable for piping and drainage installation The unit must be a large distance away from the door 400mm or more 250mm or more 1m or more Floor Standing Type 250mm or more Utensils furnitures or built in architectural features must not protrude more than 2...

Page 8: ... Þttings of the hanger bracket Set the nuts and washer on the both side of the metal Þttings Secure it with nuts Attach the hanger cover 4 pcs to the units 1 2 3 1 2 3 4 Suspension Bolt Hanger Cover Hanger Cover Suspension Bolt Hanger Rod Installation Floor Standing Type 28mm 479mm 547mm or more Mounting Bracket 509mm 458mm 301mm or more 759mm or more Rear Piping Hole Floor 123mm 78mm 40mm 307mm I...

Page 9: ...e 2 ways as illustrated The drain hose is only 1 way 1 2 Rear Piping and Drain Hose Rear Piping Hose Upper Piping OR Hook the unit on the mounting bracket Piping and Drain Hose Installation Floor Standing Type Wall OR Piping and Drain Hose Wall Piping and Drain Hose How to Install the Drain Hose Remove the two screws and the drain pipe holder Cut a slit for the drain hose hole 1 2 Place the drain ...

Page 10: ...ve the air inlet grille upward and then turn it backwards Do not use too much force Remove the grille holder both left and right side After that remove the air intake grille Remove the grille holder center from the panel 3 4 5 How to Install the Air Filter A A B B Snap in the Þlter in order to secure it Install the Þlter to the panel in the A direction follow by B to secure the Þlter To Adjust the...

Page 11: ... air intake hole at the top panel Assemble the axial fan fresh air adapter Þlter and dust hose as shown in Þgure below 1 2 2 DUCT HOSE ASSY FRESH AIR ADAPTER FILTER FRESH AIR INTAKE TOP PANEL INSTALLATION OF FRESH AIR INTAKE AHQ71AV1 ...

Page 12: ...anding and check for its alignment with the unit as shown in Figure D Also check that the hangers are secured and the base of the fan coil unit is leveled in both horizontal directions taking into account the gradient for drainage ßow as recommended in Figure E Figure D All dimensions are in mm A E B C D F G H INSTALLATION OF THE INDOOR UNIT AHQ100 125AV1 Dimension Model A B C D E F G H AHQ100AV1 ...

Page 13: ...ircuit of the cool discharge air with the warm return air Do not install the indoor unit where there is direct sunlight shining on the unit The location should be suitable for piping and drainage installation The unit must be a large distance away from the door 10 0mm or more Figure F 1m or more 400mm or more Floor Standing Type Utensils furnitures or built in architectural features must not protr...

Page 14: ... it can support the indoor unit Adjust distance to ceiling before installation Refer to dimension given to install the unit 1 2 3 Installation Ceiling Type Installation Floor Type Wall W a l l Figure G Figure H Install Indoor Units Insert the suspension bolts into the Þttings of the hanger bracket Set the nuts and washer on both side of the metal Þttings Secure it with nuts 1 2 3 ...

Page 15: ... Position the hanger rod as shown in Figure K and install the hanger bracket Figure J Figure K Step 3 Hang up the unit and tighten the bolts after installation of piping and drain pipe Please refer to Figure L Lastly install the intake grille and side panel to the correct position Please refer to Figure M Figure L Hanger Bracket Side Panel Intake grille ...

Page 16: ...Steps to open intake grille Unlock the screw attached to block lock grille with screwdriver Remove block lock grille and unlock grille lock Please refer to Figure P for reference 1 2 3 Block Lock Grille Screw M4 Close Open Figure P Drain Hose Figure N ...

Page 17: ...the rated voltage Electricity supply lines must be independent of welding transformers which can cause high supply ßuctuation Ensure that the installation location is convenient for wiring and drainage Standard Mounting Ensure that the overhead supports are strong enough to hold the weight of the unit Position the hanger rods and check for its alignment with the unit Also check that the hangers ar...

Page 18: ...unit must be a large distance away from the door Install Suspension Bolts Install the suspension bolts so that it can support the indoor unit Adjust distance to ceiling before installation Refer to dimension given by Figure S to install the unit 1 2 3 Figure S Install Indoor Units Insert the suspension bolts into the Þtting of the hanger bracket Set the nuts and washer on both side of the metal Þt...

Page 19: ...52 1 6 1 0 1 2 12 70 1 9 1 3 5 8 15 88 2 2 1 7 3 4 19 05 2 5 2 0 Pipe Size mm in Torque Nm ft lb 6 35 1 4 18 13 3 9 52 3 8 42 31 0 12 70 1 2 55 40 6 15 88 5 8 65 48 0 19 05 3 4 78 57 6 1 4t Remove burrs from cut edges of the pipes with remover as shown in Figure II This will avoid unevenness on the ßare faces which will cause gas leak Hold the pipe on top position and burr remover at lower positio...

Page 20: ... moist air Residual POE or PVE oil in the piping and components can absorb moisture from the air To prevent mischarging the diameter of the service port on the ßare valve is different from that of R22 Use tools and materials exclusively for refrigerant R410A Tools exclusively for R410A are manifold valve charging hose pressure gauge gas leak detector ßare tools torque wrench vacuum pump and refrig...

Page 21: ...MEMO LE MÉMO MITTEILUNG MEMO EL MEMORÁNDUM ПАМЯТКА NOT ΣΗΜΕΙΩΜΑ MEMO ...

Page 22: ...rtificato C 07 ËÌ ˆÛË fi ˆ Î ıÔÚ ÂÙ È ÛÙÔ A Î È ÎÚ ÓÂÙ È ıÂÙÈÎ fi ÙÔ B Û ÌÊˆÓ Ì ÙÔ ÈÛÙÔ ÔÈËÙÈÎfi C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och...

Page 23: ......

Page 24: ... la interpretación de este manual y en su traducción a cualquier idioma prevalecerá la versión inglesa El fabricante se reserva el derecho a modificar cualquiera de las especificaciones y diseños contenidos en el presente manual en cualquier momento y sin notificación previa В случае противоречия перевода данного руководства с другими переводами одного и того же текста английский вариант рассматри...

Reviews: