3600I
Page: 3
Table 1: Wiring Options
Wiring
Option
Connections Provided
1 Power
Manual
BIT
Fault Relay
N.C.
Alarm Relay
N.O.
0-20mA Sink
RS-485
-
2 Power
Manual
BIT
Fault Relay
N.C.
Alarm Relay
N.O., N.C.
0-20mA Source RS-485
HART
3 Power
Manual
BIT
Fault Relay
N.O.
Alarm Relay
N.O., N.C.
0-20mA Source RS-485
HART
4 Power
Manual
BIT
Fault Relay
N.C.
Alarm Relay
N.O.
Auxiliary N.O.
RS-485
-
5 Power
Manual
BIT
Fault Relay
N.O.
Alarm Relay
N.O.
Auxiliary N.O.
RS-485
-
Note
: Wiring option 1 is default. The mA 'Sink' output can be altered to 'Source' type,
with a link between terminals 1 and 8. No other wiring options can be changed on site.
For example, product number 3600I-321SC has the following options:
•
Wiring Option
: 3 (Power, Manual BIT, RS-485, 0-20mA (Source) with HART
Protocol, Fault Relay (N.O.), Alarm Relay (N.O., N.C.))
•
Temperature Range
: 2 (85°C)
•
Cable Entry
: 1 (M25)
•
Housing
: S (Stainless Steel)
•
Approval
: C (ATEX, IECEx)
Note
: Check your specific part numbers against the information in
Checking the Product
Type