Siemens Industry, Inc.
Building Technologies Division
P/N 315-033050-15
18
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
+
+
+
+
NC
NC
NC
NC
-
-
-
-
17
18
19
20
21
22
23
24
ZONE 2
STYLE Y
(CLASS B)
STYLE Z
(CLASS A)
ONE SLOT OF CC-5
24K,
1W
5%
24K,
1W
5%
24K,
1W
5%
ZONE 4
ZONE 3
STYLE Y
CLASS B
ZONE 1
STYLE Z
CLASS A
+
-
+
-
+
+
-
-
TO NEXT ZIC-4A
AUDIO FROM PREVIOUS
ZIC-4A OR FROM
ZAM-180 TERMINALS
1A AND 1B OR 2A AND 2B
ZAC-40/
24K,
1W
5%
NOTES
1. All wiring must be in accordance with
Article 760 of NEC or local building
codes. Wiring for each zone can
either be Class A or Class B.
2. All output circuits are power limited
to NFPA 70 per NEC 760.
3. Electrical Ratings:
Output Zone Supervisory:
4mA max
Output Zone Active:
96 Watts max / zone
4. EOL resistor, 24k ohms,
1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. For a list of Compatible Notification
Appliances, refer to P/N 315-096363.
7. Refer to CAB1/CAB1R (P/N 315-
0330007) and CAB2-BB/CAB3-BB (P/
N 315-033009) Installation Instruc-
tions for details on the separation of
power limited and non-power limited
wiring.
8. Positive or negative ground fault
detected at <40K ohms for
terminals 1-16.
Figure 13
ZIC-4A Single-Channel Audio Wiring