Siemens Industry, Inc.
Building Technologies Division
P/N 315-033050-15
16
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
+
+
+
+
NC
NC
NC
NC
NC
NC
NC
NC
-
-
-
-
+
-
+
-
+
-
+
-
+
-
17 18 19 20 21 22 23 24
BELL FOLLOWER - SECONDARY
(CLASS B)
ZONE 2
BELL FOLLOWER - SECONDARY
(CLASS B)
ZONE 4
BELL FOLLOWER - SECONDARY
(CLASS A)
ZONE 3
ONE SLOT OF CC-5
FIRE ALARM PANEL
OR
BELL EXTENDER
NAC OUTPUT SHOWN
IN ACTIVE STATE
24K,
1W
5%
24K,
1W
5%
24K,
1W
5%
BELL FOLLOWER
PRIMARY INPUT
FOR CANADIAN APPLICATIONS,
USE EOL MODEL REL-EOL.
OMIT THE DIODE.
*
*
*
*
TO PSC-12, TB4 +
TO PSC-12, TB4 -
Figure 11
ZIC-4A Bell Follower Circuit Wiring
NOTES
1. All wiring must be in accordance with Article 760 of NEC or local
building codes.
2. Only Zone 1 can be configured as Bell Follower-Primary. Any other
zone can be configured as Bell Follower-Secondary. There can only
be one Bell Follower-Primary per enclosure.
3. Electrical Ratings:
Bell Follower-Primary:
Input Alarm Current: 6mA max
Input Voltage: 24 VDC nominal
No end of line resistor is used.
Bell Follower-Secondary:
Input Voltage: 24 VDC nominal
Output Supervision Current: 4mA max
Output Alarm Current: 3A max
Output Voltage: 24 VDC nominal
4. Bell Follower-Primary is not supervised.
5. Bell Follower-Secondary is supervised for input voltage presence,
short and open on the output and is power limited. Bell Follower-
Secondary can be configured or Class A or Class B wiring.
6. The total output loop resistance must not
exceed those stated in table to the right.
7. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB
(P/N 315-033009) Installation Instructions for details on the
separation of power limited and non-power limited wiring.
8. Positive or negative ground fault detected at <40K ohms for
terminals 1-16.
9. The use of sync strobes is not allowed on the secondary circuits.
t
n
e
r
r
u
C
w
a
r
D
e
n
i
L
x
a
M
e
c
n
a
t
s
i
s
e
R
A
0
.
3
s
m
h
o
8
.
0
A
5
.
2
s
m
h
o
0
.
1
A
0
.
2
s
m
h
o
2
.
1
A
5
.
1
s
m
h
o
9
.
1
A
0
.
1
s
m
h
o
4
.
3
A
5
.
0
s
m
h
o
9
.
7