Page EN-12
XLT Series Transducers – OPERATION MANUAL
A5E32280448
Interconnection Diagram
Product Group
FOR INTERNAL USE ONLY
SIEMENS CANADA LIMITED
SIEMENS MILLTRONICS
PROCESS INSTRUMENTS
PETERBOROUGH, ONTARIO, CANADA
00027101
S. NGUYEN
PETERBOROUGH
21 DEC.1995
ULTRASONICS
FOR RELEASE
REVISED TITLE BLOCK PER ECO P5A00004758
REMOVED MILLTRONICS REFERENCE
0
1
TIEN VU
B. GRAY
1 : 1
1
1
NTS
A
XLS/XLT TRANSDUCER SERIES
INTERCONNECTION DIAGRAM
0-8830004Z-DI-A
1
BG
PJF
TV
MC
DEC
21/95
JULY
03/2012
NON - HAZARDOUS LOCATION
(SAFE)
HAZARDOUS LOCATION
CSA CLASS I, GROUP A,B,C,D
CSA CLASS II, GROUP E,F,G
JUNCTION BOX
CLASS I & II
XLS/XLT SERIES
TRANSDUCER
XLS/XLT SERIES
TRANSDUCER
METAL CONDUIT
METAL CONDUIT
CERTIFIED
CONDUIT
SEAL
FITTING
CERTIFIED
CONDUIT
SEAL
FITTING
CERTIFIED
CONDUIT
SEAL
FITTING
CERTIFIED
CONDUIT
SEAL
FITTING
SIEMENS
CONTROLLER
SIEMENS
CONTROLLER
NOTE :
2) A SEAL SHALL BE INSTALLED WITHIN 50 mm OF THE TRANSDUCER CONDUIT HUB.
3) THE TRANSDUCER DOES NOT HAVE AN INTERNAL GROUNDING PROVISION.
IT SHALL BE GROUNDED WITH THE EQUIPMENT.
4) INSTALLATION SHALL BE DONE IN ACCORDANCE WITH
CEC PART 1 REQUIREMENTS.
1) THE TRANSDUCER CABLE MUST BE TERMINATED IN AN AREA EXTERNAL
TO HAZARDOUS LOCATIONS, CLASS I & II GR. A,B,C,D,E,F,G
NON COAXIAL
COAXIAL