This manual contains information about maintenance for the 
VersiCharge Ultra 175 kW charger model: 175kW DC. 

The purpose of this document is to guide the Siemens certified 
service agent through a series of preventative maintenance 
checks for the VersiCharge Ultra 175kW DC charger system.

This guide is a living document and is updated as changes occur. 
It is the intention of Siemens to update this guide periodically as 
new procedures and technologies are developed and employed. 
The document is subject to updates without notification.

The scope of this document covers the maintenance interval 
schedule to be carried across all the sub-systems of the 
VersiCharge Ultra 175kW DC charger system. The sub-systems 
include:

  User Unit: The user unit provides an interface for the user (the  

  electric vehicle driver/owner) and  uses the CHAdeMO or  

 

  Combo 2 (CCS1) connector to connect one electric vehicle to   
  the power supply.

  Isolated power unit: The IPU outputs regulated 750 - 950 V DC  

  to the user unit. It also provides galvanic isolation of the  

 

  charging system from the AC grid  interface through the  

 

  isolation transformer, as well as charge control and      

 

  communication to back-office services.

 CRITICAL

Except as expressly stated herein, all maintenance must be 
performed by a Siemens certified service agent only. In the 
absence of a certified service agent, the actions recommended 
in this manual should not be actioned.

All maintenance work should be conducted ONLY when the site 
is completely de-energized. 

For assistance with maintenance of the charger, contact your 
supplier, or Siemens Customer Support.

Identifying symbols

 
 

CAUTION

 

 

RISK OF ELECTRIC SHOCK

 

CRITICAL

Operating temperature:

-30° to 50°C / -22 to 122°F 

 

Weather rating:

User 

unit      

IP65 

Electronics 

Enclosure 

    

NEMA Type A4

IPU

 

      

IP55 

      

NEMA Type 3R

        

CAUTION

In the event of a circuit breaker trip, the charger must be 
inspected by a Siemens-certified service agent before the 
charger is re-energized.

Important safety instructions  

 

Save these instructions

Description

Catalog No.

These VersiCharge Ultra 175™ kW DC Charger Operating                        
Instructions are for:

Dispenser Unit

US2:VSCULT175DUSAG

Transformer

US2:VSCULT175PUSAG

Maintenance Manual

 | VersiCharge Ultra 175™

3

Summary of Contents for VersiCharge Ultra 175

Page 1: ...usa siemens com versichargeultra Front Back Maintenance Manual VersiCharge Ultra 175 175 kW DC fast charger ...

Page 2: ...ant safety instructions 3 Block diagram 4 Maintenance intervals 5 User unit maintenance 6 User unit maintenance checks 7 Isolated power unit maintenance 9 Isolated power unit maintenance checks 10 Electrical safety checks 11 2 ...

Page 3: ...so provides galvanic isolation of the charging system from the AC grid interface through the isolation transformer as well as charge control and communication to back office services CRITICAL Except as expressly stated herein all maintenance must be performed by a Siemens certified service agent only In the absence of a certified service agent the actions recommended in this manual should not be a...

Page 4: ...Block diagram Simplified Detailed excluding LV board Customer LV Distribution Board Isolated Power Unit User Unit VersiCharge Ultra 175 Maintenance Manual 4 ...

Page 5: ...re tight and firm C Rear door fans filter x2 Check filter Check for airflow Clean replace as required 1 C R UPS battery Check battery controller for alerts alarms Check and replace batteries as required C R Notes 1 Filter cleaning replacement is environment dependent Perform more frequently in higher pollution environments 2 Used batteries must be disposed of in accordance with applicable national...

Page 6: ...en General exterior maintenance Regular cleaning is recommended to avoid accumulation of debris dust dirt on or around the unit Wipe surfaces with a soft cloth dampened with water or use an alcohol based cleaner for harder to remove marks Do not spray with high pressure cleaning hoses or use abrasive chemicals Snowfall areas Regularly remove snow build up if present in front of the radiator panels...

Page 7: ...notify the supplier 5 Cable Management system Pull on the cables to check the retraction system of the cables If blocked contact your supplier Coolant level and radiator fans check 1 Coolant level inspection 1 Check if the coolant is at the correct level Note The coolant should be above the level indicated by the arrows in the following image 2 If the coolant level is below the half way arrow mark...

Page 8: ...nd plugs 2 Check for cuts holes cracks sharp edges and exposed copper 3 If you observe any cuts holes cracks etc contact your supplier 4 Check the contact pins for signs of corrosion 5 If corrosion is present contact your supplier VersiCharge Ultra 175 Maintenance Manual 8 ...

Page 9: ...damage to the unit contact your supplier It is recommended to perform general maintenance at least once a year depending on the environment In harsh environments general maintenance should be performed more often General exterior maintenance Regular cleaning is recommended to avoid accumulation of debris dust dirt on or around the unit Wipe surfaces with a soft cloth dampened with water or use alc...

Page 10: ...ally as part of continuous maintenance Doors 1 Check hinges for ease of movement and spray with a suitable water free lubricant 2 Check the lock for ease of movement and spray with a suitable water free lubricant Seals 1 Check the seals for damage around the contact areas 2 If any damage replace the seal Metalwork enclosure 1 Check for signs of corrosion or damage such as scratches 2 For minor cor...

Page 11: ...elief structures 8 Retorque any screw terminals especially contactor 9 Inspect the retention of rectifier module screw terminals these cannot be retorqued 10 Check the resistance of 50 Ohm discharge resistor and 25 Ohm discharge resistor can be done with a DMM with the power off 11 Retorque and check IMD connections and terminals 12 Check AC contactors in the IPU are in the released open position ...

Page 12: ... not be relied upon for any specific application and does not constitute a performance guarantee for any projects Actual results are dependent on variable conditions Accordingly Siemens does not make representations warranties or assurances as to the accuracy currency or completeness of the content contained herein If requested we will provide specific technical data or specifications with respect...

Reviews: