background image

Table 2:  Weight & Dimensions

TPS3 12

H/W/D (in./mm.) Weight

Standard Enclosure

12" x12" x 7.5"
(305x305x191)

22 lbs
(10 kg)

Standard Enclosure, 400 – 500kA with Opt. 
Disc. Switch

16" x 14" x 6"
(496x356x152)

32 lbs
(14.5 kg)

4X Non-Metallic

14" x 12" x 7"
(356x305x178)

14 lbs
(6.4 kg)

4X  Non-Metallic,  400  –  500kA  with  Opt. 
Disc. Switch

16" x 14" x 7"
(496x356x178)

21 lbs
(9.5 kg)

4X Stainless

12" x 12" x 7"
(305x305x178)

24 lbs
(10.9 kg)

4X Stainless, 400 – 500kA with Opt. Disc. 
Switch

16" x 14" x 6"
(496x356x152)

33 lbs
(15 kg)

Pullbox & Flush mount

12" x 12" x 6”
(305x305x152)

21 lbs
(9.5 kg)

Pullbox & Flush mount, 400 – 500kA with 
Opt. Disc. Switch

16" x 14" x 6"
(496x356x152

29 lbs
(13.2 kg)

TPS3 15
Internal disconnect switch standard

Standard Enclosure

20" x 20" x 7.5"
(508x508x191)

52 lbs
(23.6 kg)

4X Non-Metallic

24" x 24" x 8"
(610x610x203)

52 lbs
(23.6 kg)

4X Stainless

20" x 20" x 7"
(508x508x178)

53 lbs
(24 kg)

Pullbox & Flush mount

20" x 20" x 6"
(508x508x152)

53 lbs
(24 kg)

Service Clearance

Service clearance is needed at the front of the unit; 36 inches minimum 
is the required distance for clearance pursuant to the NEC

®

.

Lead Lengths & Maximizing SPD Performance

SPDs must be located as close to the circuit as possible to minimize 
parasitic losses.  Surges are high current, high frequency events that 
cause substantial voltage drops across conductors.  This hurts SPD 
performance.  Use the shortest & straightest possible leads.  Pre-Plan 
installations and ensure that nearest breaker positions are used.  If 
new construction, adjust breaker locations as appropriate.

Tip:   In surge applications, voltage drops might be 100-150V 
per foot. These voltage drops add to clamping voltage, thus 
hurting performance. Make every effort to keep leads short 
and straight.

Tip:    As  distribution  gear  becomes  larger,  shorter  leads 
are  more  difficult  to  accomplish.    When  longer  leads  are 
unavoidable, gently twist leads together (one to two twists 
per foot), or tie-wrap leads together.

Shortest Leads Possible

• 

Leads must be as short and straight as possible - See NEC Art. 
285.12 

• 

No long leads

• 

No sharp bends

• 

No wire nuts

• 

How short is short enough? As short as you can make it.  

• 

How long is too long? If anyone else can make it shorter.

 

Overcurrent Protection

SPDs draw very little current under normal conditions and conduct 
for a brief duration upon encountering a transient surge current.  This 
SPD contain internal overcurrent and overtemperature protection to 
protect against abnormal voltage conditions.

Supplemental overcurrent protection is not required to protect this 
SPD. However, connecting conductors require protection in Type 2 
or 4 applications. Follow applicable codes. 

Voltage Rating

Before installing SPD, verify that it has the same voltage rating as 
the power distribution system. Compare the SPDs nameplate voltage 
or model number and ensure that SPD configuration matches the 
intended power source. See Table 1.

The specifier or the user of the device should be familiar with the 
configuration and arrangement of the power distribution system in 
which any SPD is to be installed. The system configuration of any 
power  distribution  system  is  based  strictly  on  how  the  secondary 
windings of the transformer supplying the service entrance main or 
load are configured. This includes whether or not the transformer 
windings are referenced to earth via a grounding conductor. The system 
configuration is not based on how any specific load or equipment is 
connected to a particular power distribution system.

480V System Example:  SPDs should be installed per the electrical 
system, not per a load or motor’s wiring connection.  For example, a 
480V three phase motor might appear to be connected as a 480V Delta.  
In actuality, the serving distribution system might be a 480Y/277V 
grounded Wye, with or without a neutral pulled to the motor or MCC. 
The system is still a 480Y/277V Wye, even though the load is connected 
as a Delta. A grounded Wye has a defined reference to ground (i.e., 
neutral is bonded to ground). Some Delta systems are ungrounded, 
which have no reference to ground and are known to become unstable 
in certain situations. Such instability can cause line to ground voltage 
fluctuations that may prematurely fail SPDs. For this reason, the NEC 
Article 285 has placed SPD restrictions on ungrounded systems.  As 
generalizations, SPDs for ungrounded systems can be installed on 
grounded systems with a clamping performance penalty. However, 
SPDs  for  grounded  systems  installed  on  ungrounded  systems  are 
almost certainly destined for premature failure.  Contact Tech Support 
at 1.888.333.3545 for further information.
Circuit Breaker and Disconnect Switch

The TPS3 12 and TPS3 15 family SPDs are tested and qualified as a 
Type 1 SPD per UL 1449 Third Edition and 2008 NEC. This SPD can be 
installed on the line side of the service overcurrent device per 2008 
NEC Article 285.  As a generalization, it is more practical to install on 
load side of main overcurrent device for maintenance reasons.
  
When connected on load side of main disconnect, a 60A circuit breaker 
is  recommended.  The  circuit  breaker  is  the  intended  disconnect 
switch  and  provides  short  circuit  protection  to  the  connecting 
conductors. These SPDs have internal overload protection elements 
within the product.  A breaker or disconnect is not required for the 
SPD’s overcurrent protection. These SPDs have demonstrated 200kA 
Short Circuit Current Ratings (SCCRs). 120V & 120/240V models have 
demonstrated 100kA SCCRs.  Refer to label on unit.

5

Summary of Contents for TPS3 12

Page 1: ...User Manual USA TPS3 12 TPS3 15 Surge Protective Device ...

Page 2: ...ge rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with...

Page 3: ...n Torque 6 System Grounding 6 NEMA 3R Drain Holes for Standard Steel Enclosure 6 Optional Flush Mount Installation Considerations 7 Retro fit to an Existing Panel with No Available Breaker Positions 7 Disconnect Switch Opt on TPS3 12 Std on TPS3 15 7 UL 1283 required language concerning the installation of EMI Filters 7 TPS3 12 and TPS3 15 Installation Instructions 8 Operation 10 Surge Counter Res...

Page 4: ...tion with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should be referred to the local Siemens sales office Do Not Hi Pot Test SPDs Any factory or on site testing of power distribution equipment that exceeds normal operating voltage such as high potential in...

Page 5: ...eplaceable module Do not attempt to disassemble the module as it stores charge Simplified Explanation of Operation As SPDs sense overvoltage they create a momentary internal short circuit thereby redirecting harmful surge energy to earth ground SPDs are capable of repeating this function repeatedly For optimum protection staged surge suppression should be implemented at the service entrance and al...

Page 6: ...e Current Rating TPS3 12 TPS3 L12 TPS3 15 TPS3 L15 10 100kA per phase 15 150kA per phase 20 200kA per phase 25 250kA per phase 30 300kA per phase 40 400kA per phase 45 450kA per phase 50 500kA per phase 60 600kA per phase 80 800kA per phase 90 900kA per phase 1K 1000kA per phase AVAILABLE OPTIONS When Option is Not Selected Include a 0 in the Field option code description TPS3 12 TPS3 L12 TPS3 15 ...

Page 7: ... mount or pull box enclosures are available as options Before installing ensure that your enclosure type and application are appropriate per NEMA 250 with regard to moisture dirt excessive dust flammable materials or atmospheres corrosivevapors etc Pleaseconsultfactoryifenclosure needs changed This SPD is designed to operate in an ambient temperature range of 40 C 40 F to 60 C 140 F with a relativ...

Page 8: ...e Rating Before installing SPD verify that it has the same voltage rating as the power distribution system Compare the SPDs nameplate voltage or model number and ensure that SPD configuration matches the intended power source See Table 1 The specifier or the user of the device should be familiar with the configuration and arrangement of the power distribution system in which any SPD is to be insta...

Page 9: ...tems ground impedance should be as low as possible When metallic raceway is used as an additional grounding conductor an insulated grounding conductor should be run inside the raceway and sized per the NEC Adequate electrical continuity must be maintained at all raceway connections Do not use isolating bushings to interrupt a metallic raceway run A separate isolated ground for the SPD may isolate ...

Page 10: ...oned to reduce leads See Figure 6 Models with rectangular enclosures may be repositioned by inverting only Excludes thru door handle options There is limited working space around the Disconnect Switch This is a consequence of reducing internal size and lead lengths Please be patient Disconnectswitchwillaccept6AWGto1 0AWG with6AWGpreferred Torque connections to 18 inch pounds Over torquing connecti...

Page 11: ...nfirm panel is deenergized Identify connection breaker location and SPD location Make sure leads are short Reducing inches matters InstallationTips SPDmoduleismountedonbackplanewithin its enclosure In many cases the backplane assembly can be unboltedandrotatedintwoorfourdirectionstoyieldshortest leads SeeFigure7 Carefullydisconnect ribboncable s and unbolt backplane assembly Various configurations...

Page 12: ... 0 31 DIA 4Plc 15 25 15 25 18 00 20 75 8 87 15 25 STUDS Consult factory for more options at 1 888 333 3545 A Advanced Protection Technologies Inc Clearwater Florida Listed 56E3 TVSS U R L CAUTION 2 1 3 4 6 5 7 8 Advanced Protection Technologies Inc Clearwater Florida Listed 56E3 TVSS U R L CAUTION B C N A B C N A B N C G THREE POLE C Advanced Protection Technologies Inc Clearwater Florida Listed 5...

Page 13: ...n or technician Until a qualified person evaluates the unit press Alarm Silence to silence the alarm The LED above Alarm Silence illuminates when the alarm is deactivated Normal operation occurs with the Alarm Silence LED extinguished The red Service LED will remain illuminated even though the Audible Alarm has been silenced Test tests the red Service LED the Audible Alarm and changes the state of...

Page 14: ... Service Please contact TPS Technical Support at 1 888 333 3545 for service related issues Quality SPDs are designed and tested to withstand severe duty However there are various electrical anomalies against which SPDs cannot protect These are generally Sustained Overvoltages also known as Temporary Overvoltages TOVs In this context Sustained Overvoltages may be only a few cycles Failed SPDs tend ...

Page 15: ... tabs near the inter module diagnostic wiring An illuminated red LED indicates the damaged module ExtraInformation Shouldonedamagedmoduleberemoved theSPD can still function correctly with one module If the diagnostic display cable was connected to the removed module reconnect the cable to the other module s quick release connector The diagnostic display will function correctly TPS3 15 s with Type ...

Page 16: ...Siemens Industry Inc Building Technologies Division 5400 Triangle Parkway Norcross GA 30092 888 333 3545 info us siemens com 6 17 11 jb 8172 ...

Reviews: