Introduction

Thank you for choosing Siemens TPS3 Surge Protective Device (SPD). 
This is a high quality, high energy surge suppressor designed to protect 
sensitive equipment from damaging transient overvoltages.

Proper  installation  is  important  to  maximize  performance.  Please 
follow the steps outlined herein.

This entire User Manual should be read prior to beginning installation. 
These  instructions  are  not  intended  to  replace  national  or  local 
codes. Follow all applicable electrical codes to ensure compliance. 
Installation of this SPD should only be performed by qualified electrical 
personnel.

All Siemens SPDs are extensively tested in accordance with industry 
standards such as ANSI/IEEE C62.41.1, C62.41.2, C62.45, C62.62, 
C62.72, UL 1449, UL 1283, IEC 61643, etc.

Warning and Safety Information

This equipment contains hazardous voltages. Death, serious injury, 
or property damage can result if safety instructions are not followed. 
Only qualified personnel should work on or around this equipment 
after becoming thoroughly familiar with all warnings, safety notices, 
and maintenance procedures contained herein.

The successful and safe operation of this equipment is dependent 
upon proper handling, installation, operation, and maintenance.

Qualified Person

For  the  purposes  of  this  manual  and  product  labels,  a  QUALIFIED 
PERSON is one who is familiar with the installation, construction, and 
operation of this equipment, and the hazards involved. In addition, 
he or she has the following qualifications:

(a)  Is  trained  and  authorized  to  energize,  de-energize,  clear, 

ground and tag circuits and equipment in accordance with 
established safety practices.

(b)  Is trained in the proper care and use of personal protective 

equipment  (PPE)  such  as  rubber  gloves,  hard  hat,  safety 
glasses  or  face  shields,  flash  clothing,  etc.  in  accordance 
with established safety practices. 

(c)  Is trained in rendering first aid.

Danger

For the purposes of this manual and product labels, DANGER indicates 
an imminently hazardous situation, which, if not avoided, will result 
in death or serious injury.

Warning

For the purposes of this manual and product labels, WARNING indicates 
failure  to  following  these  instructions  can  result  in  death,  serious 
injury, or equipment damage.

Caution

For the purposes of this manual and product labels, CAUTION indicates 
a potentially hazardous situation which, if not avoided, could result 
in minor or moderate injury.

These instruction do not purport to cover all details or variations in 
equipment, nor to provide for every possible contingency to be met 
in connection with installation, operation or maintenance.  Should 
further information be desired or should particular problems arise 

which are not covered sufficiently for the purchaser’s purposes, the 
matter should be referred to the local Siemens sales office.  

Do Not Hi-Pot Test SPDs

Any factory or on-site testing of power distribution equipment 
that exceeds normal operating voltage such as high-potential 
insulation testing, or any other tests where the suppression 
components will be subjected to higher voltage than their rated 
Maximum Continuous Operating Voltage (MCOV) must be con-
ducted with the SPD disconnected from the power source. For 
4-wire systems, the neutral connection at the SPD must also be 
disconnected prior to performing high-potential testing and then 
reconnected after test completion. 

Failure to disconnect SPD and associated components during 
elevated voltage testing will damage the SPD and will void the 
warranty.

Limited Warranty

Siemens warrants its AC Panel protection products against defective 
workmanship and materials for 10 years. Liability is limited to the repair 
or replacement of the defective product at Siemens’ option. A Return 
Material Authorization number (RA#) must be given by the company 
prior to the return of any product.  Returned products must be sent 
to the factory with the transportation charges prepaid.  In addition, 
the company also warranties unlimited replacement of modular and 
component parts within the warranty period previously described.

The company specifically disclaims all other warranties, expressed or 
implied. Additionally, the company is not be responsible for incidental 
or consequential damages resulting from any defect in any product 
or component thereof.

The  sales  contract  contains  the  entire  obligation  of  Siemens.  This 
instruction  manual  shall  not  become  part  of  or  modify  any  prior 
existing agreement, commitment or relationship.

Unpacking and Preliminary Inspection

Inspect  the  entire  shipping  container  for  damage  or  signs  of 
mishandling before unpacking the unit.  Remove the packing material 
and further inspect the unit  for any obvious shipping damages.  If any 
damage was found and is a result of shipping or handling, immediately 
file a claim with the shipping company and forward a copy to your local 
Siemens sales office.

Storage

The  unit  should  be  stored  in  a  clean,  dry  environment.  Storage 
temperature is -55

o

 C (-67

o

 F) to +85

o

 C (+185

o

 F). Avoid exposing 

the unit to areas of high condensation. All of the packaging materials 
should be left intact until the unit is ready for installation. If the unit 
has been stored for an extended period of time, it may be necessary 
to clean the unit and make a complete inspection of the unit prior to 
installing and placing into service.

1

Summary of Contents for TPS3 12

Page 1: ...User Manual USA TPS3 12 TPS3 15 Surge Protective Device ...

Page 2: ...ge rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with...

Page 3: ...n Torque 6 System Grounding 6 NEMA 3R Drain Holes for Standard Steel Enclosure 6 Optional Flush Mount Installation Considerations 7 Retro fit to an Existing Panel with No Available Breaker Positions 7 Disconnect Switch Opt on TPS3 12 Std on TPS3 15 7 UL 1283 required language concerning the installation of EMI Filters 7 TPS3 12 and TPS3 15 Installation Instructions 8 Operation 10 Surge Counter Res...

Page 4: ...tion with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should be referred to the local Siemens sales office Do Not Hi Pot Test SPDs Any factory or on site testing of power distribution equipment that exceeds normal operating voltage such as high potential in...

Page 5: ...eplaceable module Do not attempt to disassemble the module as it stores charge Simplified Explanation of Operation As SPDs sense overvoltage they create a momentary internal short circuit thereby redirecting harmful surge energy to earth ground SPDs are capable of repeating this function repeatedly For optimum protection staged surge suppression should be implemented at the service entrance and al...

Page 6: ...e Current Rating TPS3 12 TPS3 L12 TPS3 15 TPS3 L15 10 100kA per phase 15 150kA per phase 20 200kA per phase 25 250kA per phase 30 300kA per phase 40 400kA per phase 45 450kA per phase 50 500kA per phase 60 600kA per phase 80 800kA per phase 90 900kA per phase 1K 1000kA per phase AVAILABLE OPTIONS When Option is Not Selected Include a 0 in the Field option code description TPS3 12 TPS3 L12 TPS3 15 ...

Page 7: ... mount or pull box enclosures are available as options Before installing ensure that your enclosure type and application are appropriate per NEMA 250 with regard to moisture dirt excessive dust flammable materials or atmospheres corrosivevapors etc Pleaseconsultfactoryifenclosure needs changed This SPD is designed to operate in an ambient temperature range of 40 C 40 F to 60 C 140 F with a relativ...

Page 8: ...e Rating Before installing SPD verify that it has the same voltage rating as the power distribution system Compare the SPDs nameplate voltage or model number and ensure that SPD configuration matches the intended power source See Table 1 The specifier or the user of the device should be familiar with the configuration and arrangement of the power distribution system in which any SPD is to be insta...

Page 9: ...tems ground impedance should be as low as possible When metallic raceway is used as an additional grounding conductor an insulated grounding conductor should be run inside the raceway and sized per the NEC Adequate electrical continuity must be maintained at all raceway connections Do not use isolating bushings to interrupt a metallic raceway run A separate isolated ground for the SPD may isolate ...

Page 10: ...oned to reduce leads See Figure 6 Models with rectangular enclosures may be repositioned by inverting only Excludes thru door handle options There is limited working space around the Disconnect Switch This is a consequence of reducing internal size and lead lengths Please be patient Disconnectswitchwillaccept6AWGto1 0AWG with6AWGpreferred Torque connections to 18 inch pounds Over torquing connecti...

Page 11: ...nfirm panel is deenergized Identify connection breaker location and SPD location Make sure leads are short Reducing inches matters InstallationTips SPDmoduleismountedonbackplanewithin its enclosure In many cases the backplane assembly can be unboltedandrotatedintwoorfourdirectionstoyieldshortest leads SeeFigure7 Carefullydisconnect ribboncable s and unbolt backplane assembly Various configurations...

Page 12: ... 0 31 DIA 4Plc 15 25 15 25 18 00 20 75 8 87 15 25 STUDS Consult factory for more options at 1 888 333 3545 A Advanced Protection Technologies Inc Clearwater Florida Listed 56E3 TVSS U R L CAUTION 2 1 3 4 6 5 7 8 Advanced Protection Technologies Inc Clearwater Florida Listed 56E3 TVSS U R L CAUTION B C N A B C N A B N C G THREE POLE C Advanced Protection Technologies Inc Clearwater Florida Listed 5...

Page 13: ...n or technician Until a qualified person evaluates the unit press Alarm Silence to silence the alarm The LED above Alarm Silence illuminates when the alarm is deactivated Normal operation occurs with the Alarm Silence LED extinguished The red Service LED will remain illuminated even though the Audible Alarm has been silenced Test tests the red Service LED the Audible Alarm and changes the state of...

Page 14: ... Service Please contact TPS Technical Support at 1 888 333 3545 for service related issues Quality SPDs are designed and tested to withstand severe duty However there are various electrical anomalies against which SPDs cannot protect These are generally Sustained Overvoltages also known as Temporary Overvoltages TOVs In this context Sustained Overvoltages may be only a few cycles Failed SPDs tend ...

Page 15: ... tabs near the inter module diagnostic wiring An illuminated red LED indicates the damaged module ExtraInformation Shouldonedamagedmoduleberemoved theSPD can still function correctly with one module If the diagnostic display cable was connected to the removed module reconnect the cable to the other module s quick release connector The diagnostic display will function correctly TPS3 15 s with Type ...

Page 16: ...Siemens Industry Inc Building Technologies Division 5400 Triangle Parkway Norcross GA 30092 888 333 3545 info us siemens com 6 17 11 jb 8172 ...

Reviews: