Installation Instructions

Hazardous Voltage.
Will cause death or severe
injury.

Turn off and lock out all power supplying this
device before removing cover(s) or device
and while cover(s) are removed.

Wire connector shield no. NDTS must be
installed when wire connectors TA2K8750,
TA3P8750, TA4P8500, TA2N8750,
TA3N8750, OR TA4N8500 ARE USED.

Replace all covers and shields before power
supplying this device is turned on.

Page 

6 of 6

Pc. No.

 720658A0

3

© Siemens Energy & Automation, Inc.   1990

Neutral Sensing Transformer.

An external transformer is required for circuit break-
ers equipped with ground fault protection when op-
erating in the RESIDUAL mode on 3 phase 4 wire
systems and when operating in the GROUND RE-
TURN mode on any system. The sensors listed
below must be used for these applications. The
sensor catalog number must be matched to the cir-
cuit breaker Maximum Continuous Current rating
(In) as shown in the table. Please note that sen-

sors used with other breaker types cannot be used
with the SMD/SND circuit breakers. Installation in-
structions are included with the sensors.

Transformer

Circuit

Transformer

Catalog No.

Breaker Rating

Color

N06SMDA

600 Amps

GREEN

N07SMDA

700 Amps

GREEN

N08SMDA

800 Amps

GREEN

N10SNDA

1000 Amps

GREEN

N12SNDA

1200 Amps

GREEN

Electronic Testing

Senstrip III solid state molded case circuit break-
ers may be tested for electronic functionality by
the use of a TS-31 test set available from local
Siemens sales offices.

NOTE:  Time current characteristic curves and
information on factory installed accessories can
be obtained from local Siemens sales offices.

This product is covered by the following patent:  4,631,525.

Released Production, B v1, Dec 18, 1998

Released Production, C v1, Apr 18, 2011

Summary of Contents for SMD6

Page 1: ...nectors Mounted hardware and unmounted wire connec tors where required are available as separate cata log items Circuit Breaker Preparation A Before installing or servicing the breaker turn off and lock out all power to prevent incidental or accidental contact B Make sure that the device is suitable for the in stallation by comparing nameplate ratings with system requirements Inspect the device fo...

Page 2: ...n securely 5 Connect the line and load terminals and torque using the values shown on the circuit breaker nameplate 6 Connect all accessory terminals if present 7 Check all mounting hardware for secureness Check wire connectors for correct torque requirements Manual Operation Manual operation of the device is controlled by the circuit breaker handle and the PUSH TO TRIP button The device handle ha...

Page 3: ...rame devices are designed to provide years of maintenance free service Sensitrip III Solid State Molded Case circuit breakers may be tested for electronic functionality by the use of TS 31 test set available from local Siemens sales offices Maintenance Experience has shown that properly applied molded case circuit breakers normally do not require main tenance However some industrial users may choo...

Page 4: ...es the continuous amps setting The dia gram below illustrates the possible settings for this switch Short Time Pickup xIr Long Time Delay 6xIr The adjustable long time delay switch allows for se lection of long time delays based on I2 t curves at six time the continuous amps setting Ir The dia gram below illustrates the possible settings for this switch Continuous Amps Ir In Long Time Delay Secs 6...

Page 5: ...fault option has two modes of opera tion The mode is set by a switch on the bottom of the trip unit with the settings identified as RESIDUAL and GROUND RETURN See Fig 4 for switch lo cation RESIDUAL MODE OUTGOING CIRCUIT METHOD This is the standard position that the breaker is set to when shipped from the factory With the switch in this position the circuit breaker may be used on 3 phase 3 wire or...

Page 6: ... sensors listed below must be used for these applications The sensor catalog number must be matched to the cir cuit breaker Maximum Continuous Current rating In as shown in the table Please note that sen sors used with other breaker types cannot be used with the SMD SND circuit breakers Installation in structions are included with the sensors Transformer Circuit Transformer Catalog No Breaker Rati...

Reviews: