Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A.

Installation Instructions

Hazardous Voltage.
Will cause death or severe
injury.

Turn off and lock out all power supplying this
device before removing cover(s) or device
and while cover(s) are removed.

Wire connector shield no. NDTS must be
installed when wire connectors TA2K8750,
TA3P8750, TA4P8500, TA2N8750,
TA3N8750, OR TA4N8500 ARE USED.

Replace all covers and shields before power
supplying this device is turned on.

Page 

5 of 6

Instantaneous

Pickup
xIr

NOTE:

Breaker contains an override at multiples

of the maximum continuous current rating. These
multiples are12.5 times for 600A - 800A breakers.
Ten (10) times for 1000A breakers and 8 times for
1200A breakers. Above these levels, the short time
delay is no longer operational, and the breaker will
trip instantaneously.

Adjustable Ground Fault (optional)

Pickup Ig = % In

Delay I

2

t @.5 In

Circuit breakers with the letter “G” included in the
catalog number have intergral equipment ground
fault protection. These circuit breakers have an
adjustment to set the Ground Fault Pickup current
(Ig) as a percentage of the Maximum Continuous
Current rating (In).

The pickup has a built in time delay. Three time
delays are available of 0.1, 0.2 or 0.4 seconds.
These are selected by using the appropriate area
of the setting. Below 50% Maximum Continuous
Current rating (In), the pickup delay has an I

2

t slope.

The ground fault option has two modes of opera-
tion. The mode is set by a switch on the bottom of
the trip unit with the settings identified as RESIDUAL
and GROUND RETURN. See Fig. 4 for switch lo-
cation.

RESIDUAL MODE (OUTGOING CIRCUIT METHOD)
—This is the standard position that the breaker is
set to when shipped from the factory. With the switch
in this position, the circuit breaker may be used on
3 phase 3 wire or, with the addition of an external
neutral sensing transformer, on 3 phase 4 wire sys-
tems.

GROUND RETURN SETTING (GROUND
RETURN METHOD) — This setting may only be
used for service disconnects or separately derived
systems. With the switch in this position, the circuit
breaker may be used on 3 phase 3 wire and 3 phase
4 wire systems. An external sensing transformer,
which is installed on the main bonding jumper, is
required for this method. See Neutral Sensing
Transformer section for more information.

Instantaneous Trip  Switch

xIr

The adjustable instantaneous trip switch allows se-
lection of a tripping point from 2 to 40 times the
ampere rating. The MAX setting sets the instanta-
neous pickup to the override level (see note be-
low). The diagram below illustrates the possible set-
tings for this switch.

Ground Fault

Pickup
Ig = %In

I

2

t

Delay
@.5 In

.1s

.2s

.4s

The adjustable ground fault pickup and delay switch
allows for the selection of ground fault pickup at
various percentages of the maximum ampere rat-
ing (% In), with an I

2

t delay @.5x In of .1, .2, or .4

seconds. The diagram below illustrates the possible
settings for this switch.

MAX

40

Released Production, B v1, Dec 18, 1998

Released Production, C v1, Apr 18, 2011

Summary of Contents for SMD6

Page 1: ...nectors Mounted hardware and unmounted wire connec tors where required are available as separate cata log items Circuit Breaker Preparation A Before installing or servicing the breaker turn off and lock out all power to prevent incidental or accidental contact B Make sure that the device is suitable for the in stallation by comparing nameplate ratings with system requirements Inspect the device fo...

Page 2: ...n securely 5 Connect the line and load terminals and torque using the values shown on the circuit breaker nameplate 6 Connect all accessory terminals if present 7 Check all mounting hardware for secureness Check wire connectors for correct torque requirements Manual Operation Manual operation of the device is controlled by the circuit breaker handle and the PUSH TO TRIP button The device handle ha...

Page 3: ...rame devices are designed to provide years of maintenance free service Sensitrip III Solid State Molded Case circuit breakers may be tested for electronic functionality by the use of TS 31 test set available from local Siemens sales offices Maintenance Experience has shown that properly applied molded case circuit breakers normally do not require main tenance However some industrial users may choo...

Page 4: ...es the continuous amps setting The dia gram below illustrates the possible settings for this switch Short Time Pickup xIr Long Time Delay 6xIr The adjustable long time delay switch allows for se lection of long time delays based on I2 t curves at six time the continuous amps setting Ir The dia gram below illustrates the possible settings for this switch Continuous Amps Ir In Long Time Delay Secs 6...

Page 5: ...fault option has two modes of opera tion The mode is set by a switch on the bottom of the trip unit with the settings identified as RESIDUAL and GROUND RETURN See Fig 4 for switch lo cation RESIDUAL MODE OUTGOING CIRCUIT METHOD This is the standard position that the breaker is set to when shipped from the factory With the switch in this position the circuit breaker may be used on 3 phase 3 wire or...

Page 6: ... sensors listed below must be used for these applications The sensor catalog number must be matched to the cir cuit breaker Maximum Continuous Current rating In as shown in the table Please note that sen sors used with other breaker types cannot be used with the SMD SND circuit breakers Installation in structions are included with the sensors Transformer Circuit Transformer Catalog No Breaker Rati...

Reviews: