59
SIVACON S8 Planning Principles –
Cubicles in fixed-mounted design
2
3
4
5
6
7
8
9
10
11
1
6.2 Fixed-mounted design with
front cover
The front covers, which are easy to install, allow for the
implementation of cubicles with uniform front surfaces
(Fig. 6/2). Optionally a glass door can be used. The profile
bar design or flat copper design of the distribution busbar
allows tapping in the smallest grids. Furthermore, connec-
tions to the distribution busbars by means of cables, wires
or busbars are possible without any need of drilling or
punching. This ensures maximum flexibility also for later
expansions.
General cubicle characteristics
Tab. 6/7 summarizes the general cubicle characteristics.
The switching devices are installed on modular device
holders of graduated depth. These can be equipped with
circuit-breakers, switch-disconnectors with fuses or modu-
lar installation devices. Different switching device group-
ings into one module are also possible. Modules are at-
tached to the device holder and directly connected to the
cubicle busbar.
To the front, the devices are equipped with front covers.
Operation is effected through the cover. The cable connec-
tion is effected at the device or, in cases of higher require-
ments, at special connection terminals. For individual
expansion, the system offers freely assignable device
holders.
Tab. 6/7:
General cubicle characteristics for fixed-mounted cubicles with front cover
Application range
- Incoming feeders up to 630 A
- Outgoing cable feeders up to 630 A
- Modular installation devices
Degrees of protection
- Up to IP43
Ventilated
- IP54
Non-ventilated
Cubicle dimensions
- Cubicle height
2,000, 2,200 mm
- Cubicle width (front connection in the cubicle)
1,000, 1,200 mm
Device compartment
- Height
1,600, 1,800 mm
- Width
600 mm
Form of internal separation
- Form 1, 2b, 3b, 4a, 4b
Door,
viewing door cubicle high
1)
Design options
- Fixed-mounted module with front cover
- Mounting kit for modular installation devices
- Empty slot, device compartment
1)
Cubicle with degree of protection less than or equal to IP31 is also possible without an additional cubicle high door
Fig. 6/2:
Cubicles for fixed mounting with front cover
Summary of Contents for Sivacon S8
Page 2: ......
Page 6: ...Chapter 1 System based power distribution ...
Page 23: ...20 SIVACON S8 Planning Principles SIVACON S8 System overview ...
Page 35: ...32 SIVACON S8 Planning Principles Circuit breaker design ...
Page 93: ...90 SIVACON S8 Planning Principles Conforming to standards and design verified ...