24
SIVACON S8 Planning Principles –
Circuit-breaker design
3.1 Cubicles with one ACB (3WL)
The widths for the different cubicle types are listed by ACB
type in Tab. 3/2 to Tab. 3/4.
Tab. 3/2:
Cubicle dimensions for top busbar position
Cubicle type
ACB type
Nominal
device
current
Cubicle width in mm
Incoming / outgoing unit
Cable connection
Busbar connection
3-pole
4-pole
3-pole
4-pole
Top busbar position,
cable / busbar entry from the
top or bottom
3WL1106
630 A
400/600
600
-
-
3WL1108
800 A
400/600
600
-
-
3WL1110
1,000 A
400/600
600
-
-
3WL1112
1,250 A
400/600
600
-
-
3WL1116
1,600 A
400/600
600
400/600
600
3WL1120
2,000 A
400/600
600
400/600
600
3WL1220
2,000 A
600/800
800
600/800
800
3WL1225
2,500 A
600/800
800
600/800
800
3WL1232
3,200 A
600/800
800
600/800
800
3WL1340
4,000 A
2)
800
1,000
800
1,000
3WL1350
1)
5,000 A
2)
-
-
1,000
1,000
The position of the connecting bars is identical for cable entry
from the top or bottom
3WL1363
1)
6,300 A
2)
-
-
1,000
1,000
Longitudinal coupler
3-pole
4-pole
Top busbar position
3WL1106
630 A
600
800
-
-
3WL1108
800 A
600
800
-
-
3WL1110
1,000 A
600
800
-
-
3WL1112
1,250 A
600
800
-
-
3WL1116
1,600 A
600
800
-
-
3WL1120
2,000 A
600
800
-
-
3WL1220
2,000 A
800
1,000
-
-
3WL1225
2,500 A
800
1,000
-
-
3WL1232
3,200 A
800
1,000
-
-
3WL1340
4,000 A
2)
1,000
1,200
-
-
3WL1350
1)
5,000 A
2)
1,200
1,200
-
-
3WL1363
1)
6,300 A
2)
1,200
1,200
-
-
1)
Withdrawable design, frame height 2,200 mm
2)
Main busbar up to 6,300 A
Summary of Contents for Sivacon S8
Page 2: ......
Page 6: ...Chapter 1 System based power distribution ...
Page 23: ...20 SIVACON S8 Planning Principles SIVACON S8 System overview ...
Page 35: ...32 SIVACON S8 Planning Principles Circuit breaker design ...
Page 93: ...90 SIVACON S8 Planning Principles Conforming to standards and design verified ...