Connecting
4.2 Connection to Power
SITRANS WM300 MFA
Operating Instructions, 08/2018, A5E45090709-AA
27
●
All field wiring shall have insulation suitable for the highest applied input or relay voltage
(whichever is greater).
●
Relay contact terminals are for use with equipment that has no accessible live parts and
wiring that has insulation suitable for at least 250 V. The maximum allowable working
voltage between adjacent relay contacts should be 250 V.