
9.2.17
Upper scaling point [19]
Sets the upper range value for the scaling.
Depending on the application of the device, you set the upper scaling point as follows:
Level
Setting range:
Freely selectable numeric value
Factory setting:
100 m
Volume
Setting range:
Freely selectable numeric value
Factory setting:
1000 m
3
Volume flow
Setting range:
Freely selectable numeric value
Factory setting:
1000 m
3
/s
Mass flow
Setting range:
Freely selectable numeric value
Factory setting:
1000 kg/s
Custom units
Setting range:
Freely selectable numeric value
Factory setting:
USER DEFINED (custom), or as specified in order
9.2.17.1
Set upper scaling point
1. Navigate to the parameter view.
Navigating in the views (Page 76)
2. Select the "Upper scaling point" parameter [19].
3. Use the button to confirm.
4. Set the upper scaling point.
9.2.18
Low flow cut-off [20]
Sets the flow value for the low flow cut-off. The flow value is suppressed up to certain
percentage of the output value.
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 with 4 to 20 mA/HART
132
Operating Instructions, 11/2019, A5E44852162-AC