3EDU
Example
For the level measurement, you set the following values, for example:
Damping value:
2.0 s
Lower range value:
0.0 bar
Upper range value:
5.0 bar
Application:
Level (LEVEL)
Unit:
m
Lower scaling point:
0.0 m
Upper scaling point:
49 m
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 with 4 to 20 mA/HART
114
Operating Instructions, 11/2019, A5E44852162-AC