
<
;
P$
P$
P$
Y
Loop current or flow
X
Set measuring span
Example: Volume flow (linear)
For the volume flow measurement, you set the following values, for example:
Damping value:
2.0 s
Lower range value:
0.0 mbar
Upper range value:
0.6 bar
Application:
Linear, square root (VSLN)
Unit:
m
3
/h
Lower scaling point:
0.0 m
3
/h
Upper scaling point:
300 m
3
/h
Example: Mass flow (linear)
For the mass flow measurement, you set the following values, for example:
Damping value:
1 s
Lower range value:
0.0 mbar
Upper range value:
600 mbar
Application:
Linear, square root (MSLN)
Unit:
t/h
Lower scaling point:
0.0 t/h
Upper scaling point:
300 m
3
/ s
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
117