17
PBD-51041059
SITRANS LG260 - Operating Instructions
44284-EN-171021
1
2
1
2
Fig. 9: Fasten the probe
1 Measuring probe
2 Retaining sleeve
In case of difficult installation conditions in liquid applications, the
probe can be also mounted laterally. For this purpose, adapt the rod
with rod extensions or bow-shaped segments.
To compensate for the resulting changes in signal runtime, let the
instrument determine the probe length automatically.
The determined probe length can deviate from the actual probe
length when using curved or angled segments.
If internal installations such as struts, ladders, etc. are present on the
vessel wall, the measuring probe should be mounted at least 300 mm
(11.81 in) away from the vessel wall.
You can find further information in the supplementary instructions of
the rod extension.
In case of difficult installation conditions, for example in a socket, the
probe can be suitably adapted with a rod extension.
To compensate for the resulting changes in signal runtime, let the
instrument determine the probe length automatically.
You can find further information in the supplementary instructions of
the rod and cable components.
Lateral installation
Rod extension