Setup
3.2 Process values
FST030
Function Manual, 04/2017, A5E35693328-AA
69
3.2.9.3.5 Hysteresis
Description
Sets the hysteresis for alarm and warning limits. The hysteresis is the distance between the
limits for activation and deactivation of an alarm/warning.
Setting 0 Pa to +9999997952 Pa
Default 0.00 Pa
Related
Path
Setup → Process values → Pressure → Alarm and warning limits → Hysteresis
3.2.10
Medium temperature
3.2.10.1
Units
Description
Select units for displayed temperature. Units are not applied at communication interface.
Setting °C (degrees Celsius); °F (degrees Fahrenheit); °R (degrees Rankine); K (kelvins)
Default °C (degrees Celsius)
Related
Path
Setup
→ Process values → Medium temperature → Units
3.2.10.2
Decimal places
Description
Sets the decimal places for the process value displayed in the local display.
Setting Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal
places; 5 decimal places; 6 decimal places
Default 2 decimal places
Related
Path
Setup → Process values → Medium temperature → Decimal places
Summary of Contents for SITRANS F
Page 1: ...Function Manual Answers for industry 04 2017 Edition Ultrasonic Flowmeters FST030 SITRANS F ...
Page 2: ......
Page 18: ...Table of contents FST030 16 Function Manual 04 2017 A5E35693328 AA ...
Page 24: ...Quick Start 2 5 Copy configuration FST030 22 Function Manual 04 2017 A5E35693328 AA ...
Page 332: ...Communication 5 3 Modbus Channel 1 FST030 330 Function Manual 04 2017 A5E35693328 AA ...
Page 336: ...Security 6 8 Logout FST030 334 Function Manual 04 2017 A5E35693328 AA ...
Page 338: ...Language 7 1 Language FST030 336 Function Manual 04 2017 A5E35693328 AA ...
Page 340: ...Support A 1 Technical support FST030 338 Function Manual 04 2017 A5E35693328 AA ...
Page 346: ...Glossary FST030 344 Function Manual 04 2017 A5E35693328 AA ...
Page 348: ...Index FST030 346 Function Manual 04 2017 A5E35693328 AA ...
Page 349: ......