![Siemens SITRANS F Function Manual Download Page 103](http://html.mh-extra.com/html/siemens/sitrans-f/sitrans-f_function-manual_374463103.webp)
Setup
3.4 Inputs and outputs
FST030
Function Manual, 04/2017, A5E35693328-AA
101
1)
For channel 1 the range is 3.5 mA to 25 mA
Output scaling configuration
Below are four examples describing configuration possibilities for a current output.
Positive flow with negative scaling
①
Low flow cut-off
②
Upper range value
③
Maximum output current
④
Upper fault current
⑤
Lower range value
⑥
Lower saturation limit
⑦
Span
Current output setting
●
Process value = Mass flow
●
Direction = Positive
●
Loop current scale = 4-20 mA (maximum 25 mA)
●
Upper range value = 100 kg/h
●
Lower range value = 400 kg/h
●
Fail-safe behaviour = Upper fault current
●
Low flow cut-off = 25 kg/h
Summary of Contents for SITRANS F
Page 1: ...Function Manual Answers for industry 04 2017 Edition Ultrasonic Flowmeters FST030 SITRANS F ...
Page 2: ......
Page 18: ...Table of contents FST030 16 Function Manual 04 2017 A5E35693328 AA ...
Page 24: ...Quick Start 2 5 Copy configuration FST030 22 Function Manual 04 2017 A5E35693328 AA ...
Page 332: ...Communication 5 3 Modbus Channel 1 FST030 330 Function Manual 04 2017 A5E35693328 AA ...
Page 336: ...Security 6 8 Logout FST030 334 Function Manual 04 2017 A5E35693328 AA ...
Page 338: ...Language 7 1 Language FST030 336 Function Manual 04 2017 A5E35693328 AA ...
Page 340: ...Support A 1 Technical support FST030 338 Function Manual 04 2017 A5E35693328 AA ...
Page 346: ...Glossary FST030 344 Function Manual 04 2017 A5E35693328 AA ...
Page 348: ...Index FST030 346 Function Manual 04 2017 A5E35693328 AA ...
Page 349: ......