
SITRANS F C MASSFLO
7
SFIDK.PS.028.R1.02
ENGLISH
2. Installation
Can
only be installed in safe area!
MASS 6000 intrinsically safe data
U
o
: 16 V; I
o
: 122 mA
P
o
: 0.52 W
L
o
: 2 mH
L
o
/R
o
: 100
µ
H/
Ω
C
o
: 200 nF
2.4 Overview and
intrinsically safe data
MASS 6000 19" IP 20
& IP 65 [EEx ia] IIC
Category 1 equipment
Sensor MASS 2100 may be installed in zone 0,
zone 1 and zone 2.
MASS 2100 intrinsically safe data
See table below.
MASS 2100
EEx ia IIC T3...T6
Maximum distance between sensor MASS 2100 and signal converter MASS 6000 is 300 m with
Siemens Flow Instruments cable
FDK:
083H3005 or
FDK:
083H3006 or equivalent cable.
Cable data
Capacitance
300 [pF/m]
Self-inductance
1
[µ
H/m]
Resistance
0.05 [
Ω
/m]
Maximum length
300 [m]
C
max.
100 [nF]
L
c
/R
c
25 [
µ
H/
Ω
]
Isolation
0.25 [mm]
Temperature range
−
20
°
C to +105
°
C
Temperature range (high temperature version)
−
20
°
C to +200
°
C
Cable between MASS 2100
and MASS 6000
Terminals
1-2
3-4-9
5-6&7-8
MASS 2100
DI 1.5
DI 3
DI 6
DI 15
DI 25
DI 40
Temp.
Pick
sensor
ups
U
i
[V]
16
16
16
16
16
16
15
15
I
i
[mA]
0.132
0.132
0.132
0.132
0.132
0.132
8
15
P
i
[W]
0.75
0.75
0.75
0.75
0.75
0.75
0.03
0.056
L
i
or
[mH]
0.5
0.5 or
1.5 or
10
10
L
i
/R
i
[
µ
H/
Ω
]
80
40
30
10
15
C
i
[pF]
50
50
50
50
50
50
50
50
Equivalent cable must have L
c
/R
c
ratio lower or equal to 100 [
µ
h/
Ω]
.