Technical data
6.2 Output
SITOP PSU100C
30
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
6EP1332-5BA00
(24 V/2.5 A)
6EP1332-5BA20
(24 V/3.7 A)
6EP1332-5BA10
(24 V/4 A)
Output
Regulated, isolated DC voltage
Rated voltage value Ua rated DC
24 V
Total tolerance, static ±
3 %
3 %
3 %
Static line regulation, approx.
0.1 %
0.1 %
0.1 %
Static load regulation, approx.
0.2 %
0.2 %
0.2 %
Residual ripple peak-peak, max.
200 mV
200 mV
200 mV
Residual ripple peak-peak, typ.
55 mV
90 mV
80 mV
Spikes peak-peak, max.
(bandwidth, approx. 20 MHz)
300 mV
300 mV
300 mV
Spikes peak-peak, typ.
(bandwidth, approx. 20 MHz)
50 mV
60 mV
80 mV
Setting range
22.2…26.4 V
-
22.2…26.4 V
Product function / output voltage
can be adjusted
Yes
No
Yes
Setting the output voltage
using a potentiometer
-
using a potentiometer
Operating display
LED green for output voltage OK
Response when switching on/off
Overshoot of Ua approx. 1
%
Overshoot of Ua approx. 1
%
Starting delay, max.
0.7 s
1.5 s
1.5 ms
Voltage rise, typ.
100 ms
500 ms
400 ms
Rated current Ia rated
2.5 A
3.7 A
4 A
Current range
Remark
0…2.5 A
2.5 A to +50° C,
0.75 A to +70° C
0…3.7 A
3.7 A to +50° C,
1.1 A to +70° C
0…4 A
4 A to +50° C,
1.2 A to +70° C
Output active power / typical
60 W
89 W
96 W
Short-time overload current / for a
short circuit in operation / typical
5.5 A
5 A
13 A
Can be connected in parallel to
increase the power rating
Remark
Yes
Power-up only with single
rated load
No
Yes
Power-up only with single
rated load
Number of devices that can be
connected in parallel to increase
the power rating, units
2
-
2
Output characteristic
See Figure 6-4 24 V output characteristic (Page 31)